04/29/2024
7:33 AM

Iredell County Inspections Department

 
Permit No. AP-304594 Permit Type   BUILDING COMMERCIAL Site Address   1243 TONEWOOD ST
STATESVILLE, NC 28625
Applied   08/09/2019 Applicant  
Approved   08/09/2019 Owner   STATE FF LLC
Issued   11/08/2019 Contractor   MYERS & CHAPMAN INC
Parent Permit No.   Description   54,389 sq. ft. 95 room hotel - Fairfield Inn & Suites
  Notes  
 
  Date of Inspection Inspection Type Inspector Result Remarks Notes

LOCATION SETBACKS

 01/30/2020GRADING COMRANDALL MOOREAPPROVED

LOW VOLTAGE ROUGH

LOW VOLTAGE FINAL

 02/10/2020FOOTINGRICK CLINEPARTIAL2/10/2020 9:19:05 AM pier footings need engineers report

 02/17/2020ELEC UNDERGROUNDGERALD JOHNSONREJECTEDRequest afternoon inspection2/14/2020 1:38:50 PM 2/14/2020 1:38 PM KELLER ELECTRIC COMPANY INC Service Entrance conduits See Dustin Caudill foreman for Keller Electric Co. on-site cell#336-452-7279. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 2/17/2020 11:47:17 AM not ready

 02/18/2020ELEC UNDERGROUNDGERALD JOHNSONREJECTEDRequest late afternoon inspection2/17/2020 11:47:21 AM not ready 2/17/2020 11:47:21 AM 2/14/2020 1:38 PM KELLER ELECTRIC COMPANY INC Service Entrance conduits See Dustin Caudill foreman for Keller Electric Co. on-site cell#336-452-7279. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 2/17/2020 11:59:43 AM 2/17/2020 11:59 AM KELLER ELECTRIC COMPANY INC Service Entrance underground & UFER. See Dustin Caudill 336-452-7279. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 2/18/2020 2:13:00 PM not ready

 02/20/2020ELEC UNDERGROUNDDARIN OXENTINEPARTIALService Entrance Underground2/18/2020 2:13:05 PM not ready 2/18/2020 2:13:06 PM 2/14/2020 1:38 PM KELLER ELECTRIC COMPANY INC Service Entrance conduits See Dustin Caudill foreman for Keller Electric Co. on-site cell#336-452-7279. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 2/18/2020 2:13:06 PM not ready 2/18/2020 2:13:06 PM 2/17/2020 11:59 AM KELLER ELECTRIC COMPANY INC Service Entrance underground & UFER. See Dustin Caudill 336-452-7279. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 2/18/2020 3:02:22 PM 2/18/2020 3:02 PM KELLER ELECTRIC COMPANY INC Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 2/20/2020 10:04:25 AM rebar bond and conduits for service

WATER SUPPLY

 02/25/2020PLUMBING SLABRICK CLINEPARTIALAM PLEASE2/21/2020 12:02:07 PM partial underground 2/25/2020 1:30:16 PM marked on plans

 02/26/2020WATER SUPPLYRICK CLINEAPPROVEDeTRAKiT Inspection Request2/25/2020 1:23:28 PM 2/25/2020 1:23 PM O.H. PLUMBING INC Contact Name: O.H. PLUMBING INC Site Address: 1243 TONEWOOD ST Phone: 3362400338 e-Mail: OHPLUMBING@LEXCOMINC.NET

 03/02/2020FOOTINGRICK CLINEPARTIAL3/2/2020 1:33:02 PM 3rd party

 03/03/2020ELECTRICAL SLABDARIN OXENTINEREJECTEDSite Contact Dustin Caudill 336-452-72792/28/2020 12:18:06 PM 2/28/2020 12:18 PM KELLER ELECTRIC COMPANY INC Partial Electrical underground Slab Rough. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 3/3/2020 1:00:59 PM canceled

 03/05/2020FOOTINGRICK CLINEPARTIAL3/2/2020 1:33:07 PM 3rd party 3/5/2020 9:59:58 AM need 3rd party report

FOOTINGRICK CLINE3/5/2020 10:00:02 AM 3rd party 3/5/2020 10:00:02 AM need 3rd party report

 03/05/2020FOUNDATIONRICK CLINEPARTIALeTRAKiT Inspection Request2/17/2020 3:13:47 PM 2/17/2020 3:13 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 3/5/2020 10:00:03 AM need 3rd party report

 03/05/2020ELECTRICAL SLABPARTIALRequest AM inspections-Elect. slab rough3/5/2020 2:01:31 PM 3/5/2020 2:01 PM KELLER ELECTRIC COMPANY INC See foreman Dustin Caudill 336-452-7279. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 3/5/2020 2:16:31 PM conduits to floor boxes

 03/13/2020ELECTRICAL SLABDARIN OXENTINEPARTIALFloor Boxes3/12/2020 11:34:55 AM 3/12/2020 11:34 AM KELLER ELECTRIC COMPANY INC floor box installation Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 3/13/2020 12:12:27 PM floor boxes in office area

ELECTRICAL SLABFloor Boxes

 03/13/2020FOUNDATIONDARIN OXENTINEPARTIALeTRAKiT Inspection Request3/5/2020 10:00:08 AM need 3rd party report 3/5/2020 10:00:08 AM 2/17/2020 3:13 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 3/12/2020 6:50:27 AM 3/12/2020 6:50 AM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 3/13/2020 12:14:09 PM foundation wall for elevator. concrete is being 3rd party inspected. rebar ok ok per plan

 03/17/2020PLUMBING SLABRICK CLINEAPPROVED

 03/17/2020SLABRICK CLINEAPPROVEDeTRAKiT Inspection Request3/16/2020 7:33:35 AM 3/16/2020 7:33 AM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com

 03/17/2020PLUMBING SLABRICK CLINEAPPROVED

FOUNDATIONmasonry

 04/17/2020SHEATHING AND FLASHINGRICK CLINEPARTIALeTRAKiT Inspection Request4/16/2020 3:44:52 PM 4/16/2020 3:44 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 4/17/2020 10:39:57 AM consultation

 04/22/2020FRAMINGRICK CLINEPARTIALeTRAKiT Inspection Request4/21/2020 10:20:45 AM 4/21/2020 10:20 AM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 4/22/2020 2:43:52 PM consult

 05/22/2020ELECTRICAL ROUGHDARIN OXENTINEREJECTEDRequesting Consult by phone proposed box5/21/2020 11:33:05 AM 5/21/2020 11:33 AM KELLER ELECTRIC COMPANY INC Sent D. Oxentine email requesting approval of outlet boxes. Please call Tom Keller @ 336-667-9479 asap. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 5/22/2020 2:01:23 PM (canceled)

SHEATHING AND FLASHINGGERALD JOHNSONeTRAKiT Inspection Request5/18/2020 9:11:50 AM 5/18/2020 9:11 AM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com

 07/01/2020ELECTRICAL ROUGHDARIN OXENTINEINCOMPLETEeTRAKiT Inspection Request5/22/2020 2:01:28 PM (canceled) 5/22/2020 2:01:28 PM 5/21/2020 11:33 AM KELLER ELECTRIC COMPANY INC Sent D. Oxentine email requesting approval of outlet boxes. Please call Tom Keller @ 336-667-9479 asap. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 6/30/2020 2:42:01 PM 6/30/2020 2:42 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 7/1/2020 9:20:26 AM field consultation

 07/15/2020FRAMINGDARIN OXENTINEINCOMPLETEeTRAKiT Inspection Request7/15/2020 10:27:17 AM field consultation.

 07/15/2020FRAMINGGERALD JOHNSONAPPROVEDeTRAKiT Inspection Request

 07/24/2020ELECTRICAL ROUGHDARIN OXENTINEINCOMPLETE4th Floor OH Electrical & Corridor Walls7/22/2020 10:46:21 AM 7/22/2020 10:46 AM KELLER ELECTRIC COMPANY INC 4th Floor OH Electrical & Corridor Walls See Dustin Caudill 336-452-7279. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 7/24/2020 11:51:15 AM field consultation

 07/29/2020MECHANICAL ROUGHRICK CLINEREJECTED7/29/2020 3:01:45 PM 4th floor - installation is a deviation from the plan design. cannot tie the exhaust together.

 07/29/2020FRAMINGRICK CLINEPARTIAL7/29/2020 3:04:25 PM framing approved to allow the insulation installed in top trusses and corridor wall only

 07/30/2020ELECTRICAL ROUGHDARIN OXENTINEPARTIAL4th Floor OH Electrical & Corridor Walls7/30/2020 3:26:06 PM above ceiling only on 4th floor

 08/05/2020SEWERDARIN OXENTINEREJECTEDeTRAKiT Inspection Request8/4/2020 2:47:31 PM 8/4/2020 2:47 PM O.H. PLUMBING INC sewer line and grease trap Contact Name: O.H. PLUMBING INC Site Address: 1243 TONEWOOD ST Phone: 3362400338 e-Mail: OHPLUMBING@LEXCOMINC.NET 8/5/2020 3:58:07 PM install 2 '' vent for grease trap per plan.

 08/06/2020SEWERRICK CLINEREJECTEDeTRAKiT Inspection Request8/6/2020 11:24:51 AM Vented lids are code compliant but must be approved and documented by the designer.

 08/06/2020FRAMINGRICK CLINEPARTIAL8/6/2020 11:30:15 AM 1st floor ceiling for insultion

 08/07/2020SEWERRICK CLINEPARTIALeTRAKiT Inspection Request8/6/2020 5:35:37 AM 8/6/2020 5:35 AM O.H. PLUMBING INC Contact Name: O.H. PLUMBING INC Site Address: 1243 TONEWOOD ST Phone: 3362400338 e-Mail: OHPLUMBING@LEXCOMINC.NET 8/7/2020 2:11:01 PM down to the road

 08/07/2020ELECTRICAL ROUGHDARIN OXENTINEREJECTED3th&4th Floor OH Electrical8/7/2020 2:12:23 PM finish fire caulking on 3rd floor

 08/13/2020MECHANICAL ROUGHRICK CLINEPARTIAL4th FLOOR. WALL8/13/2020 9:37:34 AM 4th floor only, fire caulk in chase walls for bath fan exhaust.

 08/13/2020MECHANICAL ROUGHRICK CLINEPARTIAL8/13/2020 2:53:03 PM PE approval letter for the bath fan exhaust system is attached

 08/13/2020ELECTRICAL ROUGHDARIN OXENTINEREJECTED3rd Floor OH8/12/2020 12:45:12 PM 8/12/2020 12:45 PM KELLER ELECTRIC COMPANY INC 3rd Floor OH rough Electrical See David Miller 336-957-0001 Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 8/13/2020 3:48:38 PM (finish fire caulking around conduits.)

 08/14/2020FRAMINGRICK CLINEINCOMPLETEeTRAKiT Inspection Request8/13/2020 4:42:16 PM 8/13/2020 4:42 PM ben Taylor OH for 3rd floor. Plumbing is supposed to be called in also. There isn''t any HVAC required for the 3rd floor. Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com

 08/17/2020ELECTRICAL ROUGHDARIN OXENTINEREJECTED8/13/2020 3:48:43 PM (finish fire caulking around conduits.) 8/13/2020 3:48:43 PM 8/12/2020 12:45 PM KELLER ELECTRIC COMPANY INC 3rd Floor OH rough Electrical See David Miller 336-957-0001 Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 8/14/2020 2:50:28 PM 8/14/2020 2:50 PM KELLER ELECTRIC COMPANY INC Please see David Miller 336-957-0001 prior to 3 PM Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 8/17/2020 3:27:09 PM (4th floor wall rough) missing putty pads. can not use firestop box inserts when boxes are back to back per manufacture. missing knock out fillers. missing pads throughout the building and need to use putty pads for stud cavities with more than 16 square inches and where boxes are back to back. need engineer approval for plastic boxes in the bathrooms.

 08/17/2020FRAMINGRICK CLINEREJECTED3rd and 4th floors8/14/2020 3:40:37 PM 8/14/2020 3:40 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 8/17/2020 3:54:12 PM 3rd and 4th floors - electrical inspection is failed

 08/06/2020INSULATIONRICK CLINEPARTIAL4th floor - ceiling and corridor walls o8/5/2020 9:01:12 AM 8/5/2020 9:01 AM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 8/6/2020 11:27:21 AM 4th floor - ceiling and corridor walls only

 07/06/2020FRAMINGRICK CLINEPARTIAL4th OH6/29/2020 2:36:19 PM 6/29/2020 2:36 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 7/6/2020 10:55:10 AM Roof trusses only. Batt insulation may be installed after roof is complete, all trades installations is under insulation.

 09/03/2020FRAMINGRICK CLINEPARTIALeTRAKiT Inspection Request9/2/2020 6:48:33 AM 9/2/2020 6:48 AM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/3/2020 10:13:43 AM 2nd floor, all bathrooms and mech room excluded, overhead may be insulated. 3rd floor overhead except bathrooms and mech room may be sheet rocked.

 09/14/2020FRAMINGRICK CLINEREJECTEDeTRAKiT Inspection Request9/10/2020 3:32:47 PM 9/10/2020 3:32 PM ben Taylor 4th floor wall framing for insulation Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/14/2020 3:54:29 PM the electrical inspection failed

 09/15/2020ELECTRICAL ROUGHDARIN OXENTINEREJECTED4th Floor Wall Rough Electrical8/20/2020 11:00:54 AM 8/20/2020 11:00 AM KELLER ELECTRIC COMPANY INC See David Miller on-site prior to 3:00PM contact # 336-957-0001. Requesting 3rd Floor OH rough elect. inspection Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 9/10/2020 4:26:58 PM 9/10/2020 4:26 PM KELLER ELECTRIC COMPANY INC See David Miller prior to 3:00 PM- 336-957-0001 for all 4th Floor wall electrical rough Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 9/15/2020 2:28:52 PM (install putty pads where requirered see artical 714 of 2018 building code)

 09/22/2020PLUMBING ROUGHRICK CLINEPARTIAL70462283899/21/2020 4:24:31 PM 9/21/2020 4:24 PM ben Taylor Half of 4th floor. Only able to test half the floor at the time Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/22/2020 3:36:15 PM DWV and Water distribution on 4th floor north end to the mech room, fire caulking and roof drains are incomplete.

 09/22/2020ELECTRICAL ROUGHDARIN OXENTINEPARTIAL4th Floor Electrical Wall Rough9/15/2020 2:29:00 PM (install putty pads where requirered see artical 714 of 2018 building code) 9/15/2020 2:29:00 PM 8/20/2020 11:00 AM KELLER ELECTRIC COMPANY INC See David Miller on-site prior to 3:00PM contact # 336-957-0001. Requesting 3rd Floor OH rough elect. inspection Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 9/15/2020 2:29:00 PM 9/10/2020 4:26 PM KELLER ELECTRIC COMPANY INC See David Miller prior to 3:00 PM- 336-957-0001 for all 4th Floor wall electrical rough Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 9/17/2020 11:49:34 AM 9/17/2020 11:49 AM KELLER ELECTRIC COMPANY INC 4th Floor Electrical Wall Rough - AM inspection request min. prior to 3 PM. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 9/18/2020 1:21:28 PM 9/18/2020 1:21 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 4th Floor Rough Wall inspection - request AM or prior to 3PM latest. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 9/22/2020 4:46:21 PM guest rooms 4th floor

 09/22/2020ELECTRICAL ROUGHDARIN OXENTINEPARTIAL3 rd floor am9/22/2020 4:47:03 PM guest rooms 3th floor

 09/23/2020FRAMINGRICK CLINEPARTIALeTRAKiT Inspection Request9/17/2020 7:49:53 AM 9/17/2020 7:49 AM ben Taylor 2 floor over head Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/17/2020 2:44:30 PM 9/17/2020 2:44 PM ben Taylor 2 floor over head 4 floor guess room walls 1 floor corridor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/18/2020 2:04:54 PM NOT READY 9/23/2020 11:15:03 AM 3rd floor framing

 09/23/2020FRAMINGRICK CLINEAPPROVEDeTRAKiT Inspection Request9/22/2020 4:30:06 PM 9/22/2020 4:30 PM ben Taylor 3rd floor framing except for RRs. Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/23/2020 7:33:23 PM 3rd floor framing except for RRs

 09/24/2020PLUMBING ROUGHRICK CLINEPARTIALeTRAKiT Inspection Request9/15/2020 2:06:42 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/16/2020 3:24:25 PM cancelled 9/24/2020 10:56:29 AM remaining 4th floor DWV and water distribution (not insulated)

PLUMBING ROUGHRICK CLINE9/24/2020 10:56:39 AM remaining 4th floor DWV and water distribution (not insulated) 9/24/2020 10:56:39 AM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/24/2020 10:56:39 AM cancelled 10/6/2020 11:07:12 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:39 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:39 AM 3rd floor dwv, no insulation installed 1/22/2021 3:17:03 PM remaining 4th floor DWV and water distribution (not insulated) 1/22/2021 3:17:08 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/22/2021 3:17:08 PM cancelled 1/22/2021 3:17:11 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:14 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:14 PM 3rd floor dwv, no insulation installed 1/22/2021 3:17:17 PM marked on plans - phase 3 rough 1/26/2021 3:15:30 PM 1st floor guest rooms and laundry 1/26/2021 3:15:31 PM 1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC Site Contact: David Ryan 704-437-0357 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 1/26/2021 3:15:31 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:31 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:31 PM cancelled 1/26/2021 3:15:31 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:32 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:32 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:32 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:32 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:32 PM cancelled 1/26/2021 3:15:32 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:32 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:32 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:32 PM marked on plans - phase 3 rough

 09/24/2020ELECTRICAL ROUGHDARIN OXENTINEREJECTED1st & 2nd FL GR Wall Rough9/23/2020 1:49:21 PM 9/23/2020 1:49 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 1st & 2nd Floor Guestroom Wall Rough. Prior to 3:00PM please. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 9/24/2020 12:48:56 PM missing nail guards, plaster ring, ko filler and fire caulking.

 09/29/2020ELECTRICAL ROUGHDARIN OXENTINEPARTIAL2nd Floor Wall Rough9/24/2020 2:07:10 PM 9/24/2020 2:07 PM KELLER ELECTRIC COMPANY INC Please see David Miller(Keller Elect.) foreman contact =336-957-0001. Reinspect 1st&2nd GR Walls. David is on site from 8AM to Noon and 1PM till 3PM - please call David at above number to coordinate and assist in inspections. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com

 09/30/2020ELECTRICAL ROUGHDARIN OXENTINEREJECTED1st Floor Guest Rooms Wall Rough9/29/2020 3:18:20 PM 9/29/2020 3:18 PM KELLER ELECTRIC COMPANY INC Request AM please see David Miller 336-957-0001 for 1st FL GR Wall Rough Elect. request prior to noon and 3:00PM Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 9/30/2020 1:46:15 PM wire door bell in handicap rooms

 09/30/2020INSULATIONRICK CLINEPARTIALeTRAKiT Inspection Request9/23/2020 4:43:48 PM 9/23/2020 4:43 PM ben Taylor 4 floor insulation walls Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/24/2020 10:53:47 AM 4th floor rooms 9/30/2020 2:39:39 PM 3rd floor rooms

 09/30/2020FRAMINGRICK CLINEPARTIALeTRAKiT Inspection Request9/23/2020 11:15:27 AM 3rd floor framing 9/23/2020 11:15:27 AM 9/17/2020 7:49 AM ben Taylor 2 floor over head Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/23/2020 11:15:27 AM 9/17/2020 2:44 PM ben Taylor 2 floor over head 4 floor guess room walls 1 floor corridor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/23/2020 11:15:27 AM NOT READY 9/29/2020 12:21:08 PM 9/29/2020 12:21 PM ben Taylor 3 floor walls, AM would be great if we could? Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/30/2020 2:39:44 PM (2nd floor rooms only)

 10/05/2020ELECTRICAL ROUGHDARIN OXENTINEPARTIAL2nd Floor Guestroom walls10/2/2020 2:29:51 PM 10/2/2020 2:29 PM KELLER ELECTRIC COMPANY INC Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com

 10/06/2020INSULATIONRICK CLINEPARTIALeTRAKiT Inspection Request10/5/2020 9:05:33 AM 10/5/2020 9:05 AM ben Taylor 1 floor common area and hallway Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 10/6/2020 10:14:41 AM 1st floor common area and hallway overhead in TGI

 10/06/2020GAS PIPING ROUGHRICK CLINEREJECTED10/6/2020 11:06:55 AM fire chauk the floor penetrations to the roof

GAS PIPING ROUGHRICK CLINE10/6/2020 11:07:02 AM fire chauk the floor penetrations to the roof

 10/06/2020PLUMBING ROUGHRICK CLINEPARTIAL10/6/2020 11:07:04 AM roof drains test, need insulation and mid story straps

PLUMBING ROUGHRICK CLINE10/6/2020 11:07:12 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:40 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:40 AM 3rd floor dwv, no insulation installed 1/22/2021 3:17:25 PM remaining 4th floor DWV and water distribution (not insulated) 1/22/2021 3:17:25 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/22/2021 3:17:26 PM cancelled 1/22/2021 3:17:26 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:26 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:26 PM 3rd floor dwv, no insulation installed 1/22/2021 3:17:26 PM marked on plans - phase 3 rough 1/26/2021 3:15:33 PM 1st floor guest rooms and laundry 1/26/2021 3:15:33 PM 1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC Site Contact: David Ryan 704-437-0357 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 1/26/2021 3:15:33 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:33 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:33 PM cancelled 1/26/2021 3:15:33 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:33 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:34 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:34 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:34 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:34 PM cancelled 1/26/2021 3:15:34 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:34 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:34 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:34 PM marked on plans - phase 3 rough

 10/07/2020INSULATIONRICK CLINEPARTIALeTRAKiT Inspection Request9/30/2020 2:39:43 PM 3rd floor rooms 9/30/2020 2:39:43 PM 9/23/2020 4:43 PM ben Taylor 4 floor insulation walls Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/30/2020 2:39:43 PM 4th floor rooms 10/6/2020 1:47:18 PM 10/6/2020 1:47 PM ben Taylor 2 floor walls Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 10/7/2020 4:12:46 PM 2nd floor - rooms and corridor

 10/08/2020ELECTRICAL ROUGHDARIN OXENTINEPARTIAL1st FL Guestroom and GR Corridor walls10/7/2020 1:37:02 PM 10/7/2020 1:37 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for rough electrical 1st Floor Guestroom and GR Corridor 152 wall rough. request AM min. prior to 3:00PM -David at lunch noon. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com

 10/14/2020ELECTRICAL ROUGHDARIN OXENTINEPARTIAL1ST Floor Common Area walls10/9/2020 2:57:08 PM 10/9/2020 2:57 PM KELLER ELECTRIC COMPANY INC request AM inspection 1st Floor Common Areas Electrical Walls rough. See David Miller 336-957-0001 prior to 3 PM or at lunch at noon. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 10/14/2020 10:48:21 AM partial 1st floor wall rough pending pool area.

 10/15/2020FRAMINGRICK CLINEPARTIALeTRAKiT Inspection Request9/30/2020 2:39:48 PM 3rd floor framing 9/30/2020 2:39:48 PM 9/17/2020 7:49 AM ben Taylor 2 floor over head Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/30/2020 2:39:48 PM 9/17/2020 2:44 PM ben Taylor 2 floor over head 4 floor guess room walls 1 floor corridor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/30/2020 2:39:48 PM NOT READY 9/30/2020 2:39:48 PM (2nd floor rooms only) 9/30/2020 2:39:48 PM 9/29/2020 12:21 PM ben Taylor 3 floor walls, AM would be great if we could? Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 10/8/2020 4:17:48 PM 10/8/2020 4:17 PM ben Taylor 1 floor rooms Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 10/15/2020 10:20:21 AM 4th floor guest room chase floor fire proofing, and 1st floor framing per engineers approval.

 10/16/2020FRAMINGRICK CLINEPARTIAL3rd floor chase floor fire proofing10/16/2020 9:19:23 AM 3rd floor chase floor fire proofing

 10/20/2020PLUMBING ROUGHRICK CLINEINCOMPLETEeTRAKiT Inspection Request9/24/2020 10:56:40 AM remaining 4th floor DWV and water distribution (not insulated) 9/24/2020 10:56:40 AM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/24/2020 10:56:41 AM cancelled 10/6/2020 11:07:10 AM roof drains test, need insulation and mid story straps 10/19/2020 4:49:24 PM 10/19/2020 4:49 PM ben Taylor 4th floor HW and roof drain insulation Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 10/20/2020 9:34:34 AM cancelled 10/29/2020 10:36:37 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:37 AM 3rd floor dwv, no insulation installed

 10/21/2020ELECTRICAL ROUGHDARIN OXENTINEREJECTEDTemp/Perm Power MDP10/20/2020 2:09:39 PM 10/20/2020 2:09 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 Requesting Temp/Perm power to energize: MDP along with 1st FL Panels: DP1,IG & 4th FL Panel RM. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 10/21/2020 3:05:45 PM need temp power permit.

 10/22/2020INSULATIONRICK CLINEPARTIALeTRAKiT Inspection Request10/7/2020 4:12:52 PM 3rd floor rooms 10/7/2020 4:12:52 PM 9/23/2020 4:43 PM ben Taylor 4 floor insulation walls Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 10/7/2020 4:12:52 PM 4th floor rooms 10/7/2020 4:12:52 PM 2nd floor - rooms and corridor 10/7/2020 4:12:52 PM 10/6/2020 1:47 PM ben Taylor 2 floor walls Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 10/21/2020 1:22:21 PM 10/21/2020 1:22 PM ben Taylor rooms on 1 floor walls and overhead. Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 10/22/2020 2:59:05 PM 1st floor guest rooms

 10/22/2020MECHANICAL ROUGHRICK CLINEPARTIALeTRAKiT Inspection Request10/20/2020 11:30:47 AM 10/20/2020 11:30 AM ben Taylor chase wall duct seal Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 10/22/2020 3:00:16 PM duct seal in chase and 3rd and 4th floor corridor

 10/23/2020INSULATIONRICK CLINEREJECTEDeTRAKiT Inspection Request10/7/2020 4:12:51 PM 3rd floor rooms 10/7/2020 4:12:51 PM 9/23/2020 4:43 PM ben Taylor 4 floor insulation walls Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 10/7/2020 4:12:51 PM 4th floor rooms 10/7/2020 4:12:52 PM 2nd floor - rooms and corridor 10/7/2020 4:12:52 PM 10/6/2020 1:47 PM ben Taylor 2 floor walls Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 10/22/2020 1:53:37 PM 10/22/2020 1:53 PM ben Taylor chases walls gyp crete Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com

 10/26/2020TEMPORARY POWERDARIN OXENTINEAPPROVED

 10/27/2020ELECTRICAL ROUGHDARIN OXENTINEPARTIALSite Lighting Pole Bases10/26/2020 4:07:10 PM 10/26/2020 4:07 PM KELLER ELECTRIC COMPANY INC Please see David Miller on-site contact cell# 336-957-0001 - request AM inspection of Site Lighting Pole Bases. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 10/27/2020 10:21:47 AM pole bases ok.

 10/27/2020PLUMBING ROUGHRICK CLINEPARTIALPartial wall rough9/23/2020 4:40:12 PM 9/23/2020 4:40 PM ben Taylor 2ed half of 4 floor pluming Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/24/2020 10:56:35 AM remaining 4th floor DWV and water distribution (not insulated) 9/24/2020 10:56:35 AM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/24/2020 10:56:35 AM cancelled 10/6/2020 11:07:10 AM roof drains test, need insulation and mid story straps 10/26/2020 5:02:45 PM 10/26/2020 5:02 PM SERVICE PLUMBING OF CHARLOTTE INC Please see Ron on site (704)799-5459 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 10/27/2020 2:49:49 PM 3rd floor DWV north end 15 rooms and water line tested on 2nd & 3rd floors 10/29/2020 10:36:38 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:38 AM 3rd floor dwv, no insulation installed

 10/29/2020PLUMBING ROUGHRICK CLINEPARTIAL704622838910/6/2020 11:07:10 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:30 AM 3rd floor dwv, no insulation installed

PLUMBING ROUGHRICK CLINE704622838910/29/2020 10:36:40 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:40 AM 3rd floor dwv, no insulation installed 1/22/2021 3:17:28 PM remaining 4th floor DWV and water distribution (not insulated) 1/22/2021 3:17:28 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/22/2021 3:17:28 PM cancelled 1/22/2021 3:17:29 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:29 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:29 PM 3rd floor dwv, no insulation installed 1/22/2021 3:17:29 PM marked on plans - phase 3 rough 1/26/2021 3:15:35 PM 1st floor guest rooms and laundry 1/26/2021 3:15:35 PM 1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC Site Contact: David Ryan 704-437-0357 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 1/26/2021 3:15:35 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:35 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:35 PM cancelled 1/26/2021 3:15:35 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:35 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:35 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:35 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:36 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:36 PM cancelled 1/26/2021 3:15:36 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:36 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:36 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:36 PM marked on plans - phase 3 rough

 10/29/2020PLUMBING ROUGHRICK CLINEAPPROVEDPlease see Ron on site - (704)799-54599/24/2020 10:56:37 AM remaining 4th floor DWV and water distribution (not insulated) 9/24/2020 10:56:37 AM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/24/2020 10:56:37 AM cancelled 10/6/2020 11:07:11 AM roof drains test, need insulation and mid story straps 10/28/2020 3:49:20 PM 10/28/2020 3:49 PM SERVICE PLUMBING OF CHARLOTTE INC Partial Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 10/29/2020 10:36:38 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:38 AM 3rd floor dwv, no insulation installed 10/29/2020 2:04:38 PM 3rd floor dwv and water not insulation

 11/03/2020FRAMINGRICK CLINEPARTIALeTRAKiT Inspection Request10/29/2020 9:27:29 AM 10/29/2020 9:27 AM ben Taylor Restroom walls Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 11/3/2020 10:02:29 AM 4th floor bath rooms rated wall seal, chase remains

 11/03/2020INSULATIONRICK CLINEINCOMPLETEeTRAKiT Inspection Request10/29/2020 8:36:49 AM 10/29/2020 8:36 AM ben Taylor furring channel Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 11/3/2020 10:03:31 AM cancelled

 11/04/2020ELECTRICAL ROUGHDARIN OXENTINEPARTIALPartial Site Lighting Trench/Underground11/3/2020 4:01:21 PM 11/3/2020 4:01 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 Partial Site Lighting Underground/Trenching Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 11/4/2020 11:40:24 AM pole lights

 11/09/2020FRAMINGRICK CLINEPARTIALeTRAKiT Inspection Request11/6/2020 10:11:48 AM 11/6/2020 10:11 AM ben Taylor chase wall detail inspection Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 11/9/2020 10:06:04 AM 4th floor bathroom chase walls and 3rd floor bathroom ceiling

 11/09/2020ELECTRICAL ROUGHDARIN OXENTINEREJECTEDeTRAKiT Inspection Request11/6/2020 10:10:59 AM 11/6/2020 10:10 AM ben Taylor pool grounding on rebar Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 11/9/2020 2:57:25 PM wrong inspection pool permit # is AP-310425

 11/12/2020FRAMINGRICK CLINEREJECTEDnot ready11/10/2020 3:51:30 PM 11/10/2020 3:51 PM ben Taylor chase walls on 3 Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 11/12/2020 10:11:33 AM not ready

 11/17/2020FRAMINGRICK CLINEPARTIALeTRAKiT Inspection Request11/13/2020 2:06:31 PM 11/13/2020 2:06 PM ben Taylor 4 floor fire calking 3 rr ceiling Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 11/16/2020 2:22:41 PM 11/16/2020 2:22 PM ben Taylor chase walls 3 floor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com

 11/19/2020ELEC UNDERGROUNDDARIN OXENTINEPARTIALpm inspection please11/19/2020 9:00:26 AM site lights

ELEC UNDERGROUNDpm inspection please

 11/19/2020ELECTRICAL ROUGHDARIN OXENTINEPARTIAL4th Floor Guestroom OH Electrical11/13/2020 10:04:42 AM 11/13/2020 10:04 AM KELLER ELECTRIC COMPANY INC Please coordinate with David Miller 336-957-0001 for 4th Guest room OH Electrical Inspections . Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com

 11/24/2020MECHANICAL ROUGHRICK CLINEPARTIALduct seal; marked on the plans11/23/2020 11:37:02 AM 11/23/2020 11:37 AM ben Taylor duct seal for 1 and 2 floors Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 11/24/2020 2:45:33 PM duct seal; marked on the plans

 11/24/2020FRAMINGRICK CLINEPARTIAL4th floor; marked on plans11/23/2020 11:32:17 AM 11/23/2020 11:32 AM ben Taylor 3,4, floor overhead restroom and foyer ceiling Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 11/24/2020 2:46:50 PM 4th floor; marked on plans

 11/30/2020INSULATIONRICK CLINEREJECTEDeTRAKiT Inspection Request11/24/2020 10:57:31 AM 11/24/2020 10:57 AM ben Taylor Exterior wall on 1 floor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 11/30/2020 1:18:16 PM not ready

INSULATIONRICK CLINEeTRAKiT Inspection Request11/30/2020 1:18:31 PM not ready 11/30/2020 1:18:31 PM 11/24/2020 10:57 AM ben Taylor Exterior wall on 1 floor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com

INSULATIONRICK CLINEeTRAKiT Inspection Request11/30/2020 1:18:29 PM not ready 11/30/2020 1:18:29 PM 11/24/2020 10:57 AM ben Taylor Exterior wall on 1 floor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com

 12/01/2020FRAMINGRICK CLINEPARTIAL4th floor; marked on plans11/30/2020 3:49:47 PM 11/30/2020 3:49 PM ben Taylor 3 floor overhead in restrooms Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 12/1/2020 2:55:08 PM 3rd floor above ceiling inspection in rooms and foyer only. 4 inch commode riser must have a collar and some rooms (marked on plans) are not ready for dry wall.

 12/02/2020ELECTRICAL ROUGHDARIN OXENTINEREJECTED4th Floor Guestroom OH Electrical12/1/2020 5:03:05 PM 12/1/2020 5:03 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 4th Floor Electrical Panels to energize for testing GR & operate PTACs Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 12/1/2020 5:14:19 PM 12/1/2020 5:14 PM KELLER ELECTRIC COMPANY INC See David Miller=336-957-0001 for 4th Floor Electrical Panels Inspection (for testing and to energize PTACs on 4th) & 3rd floor guestroom OH Electrical. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 12/2/2020 2:33:20 PM (finish door bells)

MECHANICAL ABOVE CEILING

 12/04/2020FRAMINGRICK CLINEAPPROVED4th floor; marked on plans12/1/2020 2:55:14 PM 3rd floor above ceiling inspection in rooms and foyer only. 4 inch commode riser must have a collar and some rooms (marked on plans) are not ready for dry wall. 12/1/2020 2:55:14 PM 11/30/2020 3:49 PM ben Taylor 3 floor overhead in restrooms Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 12/3/2020 11:00:59 AM 12/3/2020 11:00 AM ben Taylor 3 floor overhead restrooms Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 12/4/2020 3:00:03 PM all framing is complete, use above ceiling inspection request

 12/11/2020ELECTRICAL ROUGHDARIN OXENTINEREJECTED3rd FL Panels & 2nd G Rooms OH rough12/2/2020 2:33:23 PM (finish door bells) 12/2/2020 2:33:23 PM 12/1/2020 5:03 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 4th Floor Electrical Panels to energize for testing GR & operate PTACs Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 12/2/2020 2:33:23 PM 12/1/2020 5:14 PM KELLER ELECTRIC COMPANY INC See David Miller=336-957-0001 for 4th Floor Electrical Panels Inspection (for testing and to energize PTACs on 4th) & 3rd floor guestroom OH Electrical. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 12/10/2020 5:43:20 PM 12/10/2020 5:43 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 3rd Floor Panel inspection for the purpose of Operating PTACs and Testing along with 3rd Floor Guestroom OH Electrical Rough. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 12/10/2020 5:50:14 PM 12/10/2020 5:50 PM KELLER ELECTRIC COMPANY INC 3rd Floor panels to operate PTACs and testing & 2nd Floor Guestroom OH electrical Rough Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 12/11/2020 10:11:54 AM canceled

 12/16/2020BUILDING ABOVE CEILINGRICK CLINEINCOMPLETEeTRAKiT Inspection Request12/14/2020 1:10:58 PM 12/14/2020 1:10 PM ben Taylor 2 floor restroom furors Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 12/16/2020 7:13:38 AM cancelled

 12/16/2020ELECTRICAL ROUGHDARIN OXENTINEPARTIAL3rd Floor panels to operated PTACs /test12/14/2020 12:10:55 PM 12/14/2020 12:10 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 to inspect 3rd floor panels to operate PTAC''s & Testing Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com

 12/16/2020ELEC ABOVE CEILINGDARIN OXENTINEPARTIAL

 12/16/2020ELEC ABOVE CEILINGDARIN OXENTINEPARTIAL2nd FL GR OH Rough12/15/2020 11:45:25 AM 12/15/2020 11:45 AM KELLER ELECTRIC COMPANY INC See David Miller for 2nd Floor Guest Rooms OH Electrical Rough inspection. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com

 12/18/2020PLUMBING ROUGHRICK CLINEREJECTEDPartial 1st floor rough9/24/2020 10:56:36 AM remaining 4th floor DWV and water distribution (not insulated) 9/24/2020 10:56:36 AM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/24/2020 10:56:36 AM cancelled 10/6/2020 11:07:11 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:38 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:38 AM 3rd floor dwv, no insulation installed 12/17/2020 5:19:43 PM 12/17/2020 5:19 PM SERVICE PLUMBING OF CHARLOTTE INC Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 12/18/2020 1:55:04 PM north end of 1st- install mid story guides, support wtr lines and insulate, install fire stops (tests are good)

 12/23/2020PLUMBING ROUGHRICK CLINEPARTIALeTRAKiT Inspection Request9/24/2020 10:56:38 AM remaining 4th floor DWV and water distribution (not insulated) 9/24/2020 10:56:38 AM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/24/2020 10:56:38 AM cancelled 10/6/2020 11:07:11 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:38 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:39 AM 3rd floor dwv, no insulation installed 12/22/2020 1:56:50 PM 12/22/2020 1:56 PM ben Taylor phase 1 and 2 DWV and water Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 12/23/2020 4:04:58 PM 1st floor phase 1 walls only 12/28/2020 8:11:14 AM 1st floor phase 1 walls only

 01/04/2021BUILDING ABOVE CEILINGRICK CLINEPARTIALeTRAKiT Inspection Request12/23/2020 5:16:12 PM 12/23/2020 5:16 PM ben Taylor 2 floor overhead ceiling guess rooms and restrooms Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/4/2021 1:39:41 PM marked on the plans

 01/05/2021ELECTRICAL ROUGHDARIN OXENTINEPARTIALsee notes1/4/2021 2:57:40 PM 4th floor corridor and all stairwells, 2nd floor electric panels

 01/06/2021BUILDING ABOVE CEILINGRICK CLINEREJECTED4th corridor & public gang toilet chase1/6/2021 3:45:41 PM rejection is marked on the plans

 01/08/2021BUILDING ABOVE CEILINGRICK CLINEREJECTED4th floor AC in corridor1/7/2021 5:24:39 PM 1/7/2021 5:24 PM ben Taylor We submitted an RFI for damper at elevator and came back that no damper was needed. See Will to discuss. Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/8/2021 10:19:44 AM marked on the plans

 01/13/2021BUILDING ABOVE CEILINGRICK CLINEPARTIAL4th floor AC in corridor1/8/2021 10:19:50 AM marked on the plans 1/8/2021 10:19:50 AM 1/7/2021 5:24 PM ben Taylor We submitted an RFI for damper at elevator and came back that no damper was needed. See Will to discuss. Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/12/2021 7:10:25 AM 1/12/2021 7:10 AM ben Taylor Please notify once on site. Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/13/2021 11:01:10 AM 4th floor over head is approved

 01/15/2021ELEC ABOVE CEILINGDARIN OXENTINEPARTIAL3rd Floor Corridor Above Ceilings1/13/2021 4:23:32 PM 1/13/2021 4:23 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 requesting 3rd Floor corridor above ceiling inspection. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 1/15/2021 8:51:46 AM 3rd floor corridor above ceiling

 01/20/2021BUILDING ABOVE CEILINGDARIN OXENTINEPARTIAL4th floor AC in corridor1/13/2021 11:01:26 AM marked on the plans 1/13/2021 11:01:26 AM 1/7/2021 5:24 PM ben Taylor We submitted an RFI for damper at elevator and came back that no damper was needed. See Will to discuss. Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/13/2021 11:01:26 AM 4th floor over head is approved 1/13/2021 11:01:27 AM 1/12/2021 7:10 AM ben Taylor Please notify once on site. Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/18/2021 3:12:59 PM 1/18/2021 3:13 PM ben Taylor 3rd floor above ceiling inspection Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/20/2021 3:13:28 PM 3rd floor corridor

 01/22/2021ELECTRICAL ROUGHDARIN OXENTINEINCOMPLETEPanel 1A1/20/2021 2:40:42 PM 1/20/2021 2:40 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001, request PM inspection Panel 1A Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 1/22/2021 2:42:18 PM canceled

 01/22/2021PLUMBING ROUGHRICK CLINEPARTIAL9/24/2020 10:56:38 AM remaining 4th floor DWV and water distribution (not insulated) 9/24/2020 10:56:38 AM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/24/2020 10:56:39 AM cancelled 10/6/2020 11:07:12 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:39 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:39 AM 3rd floor dwv, no insulation installed 1/22/2021 3:16:51 PM marked on plans - phase 3 rough

PLUMBING ROUGHRICK CLINEPartial 1st floor rough1/22/2021 3:17:29 PM remaining 4th floor DWV and water distribution (not insulated) 1/22/2021 3:17:29 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/22/2021 3:17:29 PM cancelled 1/22/2021 3:17:29 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:30 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:30 PM 3rd floor dwv, no insulation installed 1/22/2021 3:17:30 PM marked on plans - phase 3 rough 1/26/2021 3:15:36 PM 1st floor guest rooms and laundry 1/26/2021 3:15:36 PM 1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC Site Contact: David Ryan 704-437-0357 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 1/26/2021 3:15:37 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:37 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:37 PM cancelled 1/26/2021 3:15:37 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:37 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:37 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:37 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:37 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:37 PM cancelled 1/26/2021 3:15:38 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:38 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:38 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:38 PM marked on plans - phase 3 rough

PLUMBING ROUGHRICK CLINEeTRAKiT Inspection Request1/22/2021 3:17:30 PM remaining 4th floor DWV and water distribution (not insulated) 1/22/2021 3:17:30 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/22/2021 3:17:30 PM cancelled 1/22/2021 3:17:30 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:30 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:30 PM 3rd floor dwv, no insulation installed 1/22/2021 3:17:31 PM marked on plans - phase 3 rough 1/26/2021 3:15:38 PM 1st floor guest rooms and laundry 1/26/2021 3:15:38 PM 1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC Site Contact: David Ryan 704-437-0357 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 1/26/2021 3:15:38 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:38 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:39 PM cancelled 1/26/2021 3:15:39 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:39 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:39 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:39 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:39 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:39 PM cancelled 1/26/2021 3:15:39 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:39 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:40 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:40 PM marked on plans - phase 3 rough

PLUMBING ROUGHRICK CLINE1/22/2021 3:17:31 PM remaining 4th floor DWV and water distribution (not insulated) 1/22/2021 3:17:31 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/22/2021 3:17:31 PM cancelled 1/22/2021 3:17:31 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:31 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:31 PM 3rd floor dwv, no insulation installed 1/22/2021 3:17:31 PM marked on plans - phase 3 rough 1/26/2021 3:15:40 PM 1st floor guest rooms and laundry 1/26/2021 3:15:40 PM 1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC Site Contact: David Ryan 704-437-0357 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 1/26/2021 3:15:40 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:40 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:40 PM cancelled 1/26/2021 3:15:40 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:41 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:41 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:41 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:41 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:41 PM cancelled 1/26/2021 3:15:41 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:41 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:41 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:41 PM marked on plans - phase 3 rough

PLUMBING ROUGHRICK CLINEeTRAKiT Inspection Request1/22/2021 3:17:26 PM remaining 4th floor DWV and water distribution (not insulated) 1/22/2021 3:17:26 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/22/2021 3:17:27 PM cancelled 1/22/2021 3:17:27 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:27 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:27 PM 3rd floor dwv, no insulation installed 1/22/2021 3:17:27 PM marked on plans - phase 3 rough 1/26/2021 3:15:42 PM 1st floor guest rooms and laundry 1/26/2021 3:15:42 PM 1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC Site Contact: David Ryan 704-437-0357 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 1/26/2021 3:15:42 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:42 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:42 PM cancelled 1/26/2021 3:15:42 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:42 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:43 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:43 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:43 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:43 PM cancelled 1/26/2021 3:15:43 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:43 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:43 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:43 PM marked on plans - phase 3 rough

PLUMBING ROUGHRICK CLINEPartial wall rough1/19/2021 11:40:21 AM 1/19/2021 11:40 AM SERVICE PLUMBING OF CHARLOTTE INC Site contact: Ron (704)799-5459 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 1/22/2021 3:17:27 PM remaining 4th floor DWV and water distribution (not insulated) 1/22/2021 3:17:27 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/22/2021 3:17:27 PM cancelled 1/22/2021 3:17:28 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:28 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:28 PM 3rd floor dwv, no insulation installed 1/22/2021 3:17:28 PM marked on plans - phase 3 rough 1/26/2021 3:15:44 PM 1st floor guest rooms and laundry 1/26/2021 3:15:44 PM 1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC Site Contact: David Ryan 704-437-0357 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 1/26/2021 3:15:44 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:44 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:44 PM cancelled 1/26/2021 3:15:44 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:44 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:44 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:44 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:45 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:45 PM cancelled 1/26/2021 3:15:45 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:45 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:45 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:45 PM marked on plans - phase 3 rough

 01/26/2021PLUMBING ROUGHRICK CLINEPARTIAL1st floor rough complete9/24/2020 10:56:40 AM remaining 4th floor DWV and water distribution (not insulated) 9/24/2020 10:56:40 AM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 9/24/2020 10:56:40 AM cancelled 10/6/2020 11:07:12 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:39 AM roof drains test, need insulation and mid story straps 10/29/2020 10:36:40 AM 3rd floor dwv, no insulation installed 1/22/2021 3:17:20 PM remaining 4th floor DWV and water distribution (not insulated) 1/22/2021 3:17:23 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/22/2021 3:17:25 PM cancelled 1/22/2021 3:17:25 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:25 PM roof drains test, need insulation and mid story straps 1/22/2021 3:17:25 PM 3rd floor dwv, no insulation installed 1/22/2021 3:17:25 PM marked on plans - phase 3 rough 1/25/2021 10:27:12 AM 1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC Site Contact: David Ryan 704-437-0357 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 1/26/2021 3:15:10 PM 1st floor guest rooms and laundry

PLUMBING ROUGHRICK CLINE1st floor rough complete1/26/2021 3:15:47 PM 1st floor guest rooms and laundry 1/26/2021 3:15:47 PM 1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC Site Contact: David Ryan 704-437-0357 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 1/26/2021 3:15:47 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:47 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:47 PM cancelled 1/26/2021 3:15:47 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:47 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:48 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:48 PM remaining 4th floor DWV and water distribution (not insulated) 1/26/2021 3:15:48 PM 9/15/2020 2:06 PM ben Taylor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/26/2021 3:15:48 PM cancelled 1/26/2021 3:15:48 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:48 PM roof drains test, need insulation and mid story straps 1/26/2021 3:15:48 PM 3rd floor dwv, no insulation installed 1/26/2021 3:15:49 PM marked on plans - phase 3 rough

 01/28/2021ELEC ABOVE CEILINGDARIN OXENTINEREJECTED2nd Floor Corridor OH1/25/2021 2:59:15 PM 1/25/2021 2:59 PM KELLER ELECTRIC COMPANY INC See David Miller for 2nd Floor Corridor OH inspection. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 1/28/2021 6:34:43 AM tie two lights on south end of corridor to structure

 02/01/2021ELECTRICAL ROUGHDARIN OXENTINEREJECTEDeTRAKiT Inspection Request1/29/2021 1:24:45 PM 1/29/2021 1:24 PM ben Taylor Bonding on the pool equ. Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 2/1/2021 3:43:37 PM wrong permit. pool permit # is AP-310425

ELECTRICAL ROUGHeTRAKiT Inspection Request

 02/02/2021GAS PIPING FINALRICK CLINEAPPROVED

 02/02/2021MECHANICAL ROUGHRICK CLINEINCOMPLETEAir test2/1/2021 3:19:07 PM 2/1/2021 3:19 PM SERVICE PLUMBING OF CHARLOTTE INC Site contact: Ron (704)799-5459 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 2/2/2021 3:25:21 PM this is a gas inspection request

MECHANICAL ROUGH

 02/02/2021GAS PIPING ROUGHRICK CLINEAPPROVED10/6/2020 11:07:03 AM fire chauk the floor penetrations to the roof

 02/04/2021BUILDING ABOVE CEILINGRICK CLINEPARTIALeTRAKiT Inspection Request1/20/2021 3:13:33 PM marked on the plans 1/20/2021 3:13:33 PM 1/7/2021 5:24 PM ben Taylor We submitted an RFI for damper at elevator and came back that no damper was needed. See Will to discuss. Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/20/2021 3:13:33 PM 4th floor over head is approved 1/20/2021 3:13:33 PM 1/12/2021 7:10 AM ben Taylor Please notify once on site. Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 1/20/2021 3:13:33 PM 3rd floor corridor 1/20/2021 3:13:33 PM 1/18/2021 3:13 PM ben Taylor 3rd floor above ceiling inspection Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 2/2/2021 10:03:42 AM 2/2/2021 10:03 AM ben Taylor Chase wall in guess rooms rr Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 2/4/2021 2:24:07 PM marked on plans

 02/08/2021ELEC ABOVE CEILINGDARIN OXENTINEREJECTED1st Floor partial OH hard ceilings right2/5/2021 11:09:54 AM 2/5/2021 11:09 AM KELLER ELECTRIC COMPANY INC See David Miller: 336-957-0001, 1st Floor Partial OH -Right side of building - to cover hard ceiling areas only. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 2/8/2021 1:22:32 PM missing covers, need access to all switches above hard ceiling, finish low volt, and mc cable can not be on the grid.

 02/09/2021BUILDING ABOVE CEILINGRICK CLINEINCOMPLETEeTRAKiT Inspection Request2/8/2021 1:09:17 PM 2/8/2021 1:09 PM ben Taylor Overhead phases 1 and 2. Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 2/9/2021 9:08:18 AM cancelled

 02/11/2021ELEC ABOVE CEILINGDARIN OXENTINEPARTIAL1st Floor Partial OH Elect. Hard Ceiling2/9/2021 2:37:54 PM 2/9/2021 2:37 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 1st Floor Right Side-Partial OH Elect. Hard ceiling areas reinspection. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com

 02/15/2021BUILDING ABOVE CEILINGRICK CLINEINCOMPLETEeTRAKiT Inspection Request2/13/2021 9:36:10 AM 2/13/2021 9:36 AM ben Taylor All sheetrock ceilings right side of lobby including corridor Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com

 02/16/2021ELEC ABOVE CEILINGDARIN OXENTINEPARTIALOH Electrical Center Sect. hard ceilings2/15/2021 4:27:07 PM 2/15/2021 4:27 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 requesting OH Electrical for Center section Hard Ceilings = Lobby/Buffett drywall & wood ceilings of center section common areas. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 2/16/2021 12:19:33 PM lobby area

 02/16/2021BUILDING ABOVE CEILINGRICK CLINEPARTIALeTRAKiT Inspection Request2/15/2021 5:36:22 PM 2/15/2021 5:36 PM ben Taylor phases 1 and 2 Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 2/16/2021 2:35:16 PM north end of 1st floor hard ceiling space only

 02/17/2021BUILDING ABOVE CEILINGRICK CLINEPARTIALeTRAKiT Inspection Request2/16/2021 4:01:06 PM 2/16/2021 4:01 PM ben Taylor lobby Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 2/17/2021 2:47:54 PM hard ceiling only in lobby and vestibule

 02/18/2021BUILDING ABOVE CEILINGRICK CLINEREJECTEDeTRAKiT Inspection Request2/17/2021 4:46:46 PM 2/17/2021 4:46 PM ben Taylor ceiling in the lobby Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 2/18/2021 11:20:45 AM beams across lobby ceiling requires two layers of sheetrock

 02/23/2021BUILDING ABOVE CEILINGRICK CLINEPARTIALeTRAKiT Inspection Request2/18/2021 11:20:56 AM beams across lobby ceiling requires two layers of sheetrock 2/18/2021 11:20:56 AM 2/17/2021 4:46 PM ben Taylor ceiling in the lobby Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 2/21/2021 10:43:52 AM 2/21/2021 10:43 AM ben Taylor above ceiling on all still beams Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 2/23/2021 9:42:56 AM beams wrapped

 02/24/2021ELEC ABOVE CEILINGDARIN OXENTINEPARTIAL1st Floor GR Baths OH rough & Vestibule2/23/2021 11:32:02 AM 2/23/2021 11:32 AM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 1st Floor GR Bathrooms OH rough Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 2/23/2021 12:14:41 PM 2/23/2021 12:14 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 1st Floor guestroom bathroom OH rough & front Vestibule OH rough. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 2/24/2021 11:27:48 AM bathrooms 1st floor only

ELEC ABOVE CEILINGDARIN OXENTINE1st Floor above ceiling GR Entry & Room2/24/2021 11:28:00 AM bathrooms 1st floor only 2/24/2021 11:28:00 AM 2/23/2021 11:32 AM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 1st Floor GR Bathrooms OH rough Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 2/24/2021 11:28:00 AM 2/23/2021 12:14 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 1st Floor guestroom bathroom OH rough & front Vestibule OH rough. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 2/25/2021 1:28:23 PM 2/25/2021 1:28 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 1st Floor Above Ceiling Guestroom Entry & Maintenance/Storage 143. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 3/2/2021 11:14:35 AM 10 guest rooms 1st floor ok to hang. Missing covers on 6x6 boxes, need to leave access doors open.

 03/02/2021PLUMBING FINAL CERT OF COMPRICK CLINEPARTIAL2nd, 3rd & 4th Floors3/1/2021 10:19:22 AM 3/1/2021 10:19 AM SERVICE PLUMBING OF CHARLOTTE INC Site contact: Ron (704)799-5459 Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net 3/2/2021 10:51:28 AM 2nd, 3rd, & 4th, all good except the tank flush handle must be on open side of room

PLUMBING FINAL CERT OF COMP2nd, 3rd & 4th Floors

 03/02/2021MECHANICAL FINAL CERT OF COMPRICK CLINEPARTIALeTRAKiT Inspection Request2/25/2021 3:33:49 PM 2/25/2021 3:33 PM ben Taylor Mechanical final on 3 and 4 floors Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 3/2/2021 10:57:24 AM 2nd, 3rd, & 4th floors

 03/02/2021BUILDING ABOVE CEILINGRICK CLINEPARTIALeTRAKiT Inspection Request3/2/2021 10:59:51 AM guest room foyers on 1st floor ok to hang

 03/02/2021ELEC ABOVE CEILINGDARIN OXENTINEPARTIALGUEST ROOMS AND LAUNDRY ROOM3/3/2021 8:23:16 AM 10 guest rooms 1st floor ok to hang. Missing covers on 6x6 boxes, need to leave access doors open

 03/02/2021ELECTRICAL FINAL CERT OF COMPDARIN OXENTINEREJECTED3rd and 4th floor3/3/2021 8:26:38 AM Bath fans not working properly. GFI's and receptacles not tightened too tight. Missing covers on boxes. Need to cap wiring to mechanical blinds or install blinds. Occupancy sensors don't work properly in guest rooms. Switches recessed too far in boxes in bathrooms

 03/02/2021TEMPORARY POWERDARIN OXENTINEAPPROVEDrenew 2/26-4/26/2021

 03/05/2021BUILDING ABOVE CEILINGRICK CLINEPARTIALeTRAKiT Inspection Request3/3/2021 3:47:02 PM 3/3/2021 3:47 PM ben Taylor Landry and back of house Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com

 03/05/2021ELECTRICAL FINAL CERT OF COMPDARIN OXENTINEPARTIAL4th Floor Final Elect.3/4/2021 4:27:58 PM 3/4/2021 4:27 PM KELLER ELECTRIC COMPANY INC See Josh Absher 336-426-4314 to reinspect 4th & 3rd Floor Final Electrical. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 3/5/2021 4:21:36 PM 4th floor only

 03/05/2021ELEC ABOVE CEILINGDARIN OXENTINEREJECTED1st Floor multi room OH Electrical3/4/2021 4:30:36 PM 3/4/2021 4:30 PM KELLER ELECTRIC COMPANY INC See Josh Absher 336-426-4314 for 1st Floor: Guest Laundry, Guestroom Corridor, Food Prep, Board Room OH Electrical. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 3/5/2021 4:23:04 PM lower or install box extensions in quest rooms.

 03/09/2021ELEC ABOVE CEILINGDARIN OXENTINEAPPROVED1st Floor OH Electrical multi room3/8/2021 2:28:51 PM 3/8/2021 2:28 PM KELLER ELECTRIC COMPANY INC See Josh Absher 336-426-4314 for 1st Floor: Guest Laundry, Guestroom Corridor, Food Prep, Board Room OH Electrical. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com

 03/11/2021BUILDING ABOVE CEILINGRICK CLINEPARTIALeTRAKiT Inspection Request3/10/2021 3:32:57 PM 3/10/2021 3:32 PM ben Taylor lobby, board room, Contact Name: ben Taylor Site Address: 1243 TONEWOOD ST Phone: 7049600842 e-Mail: btaylor@myers-chapman.com 3/11/2021 10:18:10 AM marked on the plans

BUILDING ABOVE CEILINGeTRAKiT Inspection Request

 03/12/2021ELECTRICAL FINAL CERT OF COMPDARIN OXENTINEPARTIAL3rd Floor Final Electrical3/11/2021 1:34:34 PM 3/11/2021 1:34 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 3rd Floor Final Electrical inspection. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com

 03/17/2021ELECTRICAL FINAL CERT OF COMPDARIN OXENTINEPARTIAL2nd Floor Final Electrical2/25/2021 1:24:56 PM 2/25/2021 1:24 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 4th Floor Final Electrical Inspection. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 3/2/2021 11:14:36 AM Bath fans not working properly. GFI's and receptacles not tightened/too tight. Missing covers on boxes. Need to cap wiring to mechanical blinds or install blinds. Occupancy sensors don't work properly in guest rooms. Switches recessed too far in boxes in bathrooms. 3/15/2021 10:02:19 AM 3/15/2021 10:02 AM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 2nd Floor Final Electrical Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 3/17/2021 8:46:48 AM 2nd floor

 03/29/2021ELECTRICAL FINAL CERT OF COMPDARIN OXENTINEPARTIAL1st floor guest rooms3/26/2021 11:01:37 AM 3/26/2021 11:01 AM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for final electrical inspection of 1st Floor Guestrooms, GR Corridor 152 & Guest Laundry 151. Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com 3/29/2021 12:08:43 PM 1st floor guest rooms

ELECTRICAL FINAL CERT OF COMP1st floor guest rooms

 03/31/2021ELECTRICAL FINAL CERT OF COMPDARIN OXENTINEPARTIALroof ok3/30/2021 1:44:19 PM 3/30/2021 1:44 PM KELLER ELECTRIC COMPANY INC See David Miller 336-957-0001 for 1st Floor Final Electrical Contact Name: KELLER ELECTRIC COMPANY INC Site Address: 1243 TONEWOOD ST Phone: 3366679479 e-Mail: tom@kellernc.com

 04/01/2021FIRE FINAL CERT OF COMPC MAURY JENKINSAPPROVED

 04/07/2021BACKFLOWRegina A HokeAPPROVED

 04/12/2021ELECTRICAL FINAL CERT OF COMPDARIN OXENTINEAPPROVEDroof ok

 04/19/2021ZONING FINALELAINE ANTHONYAPPROVED

 04/23/2021BLDG FINAL CERT OF COMPRICK CLINEREJECTED4/23/2021 4:10:13 PM sewer not approved, hole in corridor wall over laundry room, paint the gas pipe on roof, break room toilet grab bar not secure, remove locks from gang bath doors, install clean out cover in front yard, multible holes remain un caulked (Tim was with me). screens are prohibited on dryer duct terminations.

 04/23/2021MECHANICAL FINAL CERT OF COMPRICK CLINEAPPROVEDeTRAKiT Inspection Request

 04/23/2021SEWERRICK CLINEREJECTEDeTRAKiT Inspection Request4/23/2021 11:10:48 AM tracer wire is not in place

SEWERRICK CLINEeTRAKiT Inspection Request4/23/2021 11:10:56 AM tracer wire is not in place

 04/23/2021PLUMBING FINAL CERT OF COMPRICK CLINEAPPROVEDRon (704)799-5459 (Site Contact)2/25/2021 12:55:08 PM 2/25/2021 12:55 PM SERVICE PLUMBING OF CHARLOTTE INC 2nd, 3rd & 4th Floors Contact Name: SERVICE PLUMBING OF CHARLOTTE INC Site Address: 1243 TONEWOOD ST Phone: 7048958998 e-Mail: jjones@serviceplumbing.net

 04/26/2021BLDG FINAL CERT OF COMPRICK CLINEAPPROVED4/23/2021 4:13:37 PM sewer not approved, hole in corridor wall over laundry room, paint the gas pipe on roof, break room toilet grab bar not secure, remove locks from gang bath doors, install clean out cover in front yard, multible holes remain un caulked (Tim was with me) screens on dryer vents are prohibited

 04/26/2021SEWERRICK CLINEAPPROVEDeTRAKiT Inspection Request4/23/2021 11:10:59 AM tracer wire is not in place

 04/26/2021CERT OF OCCUPANCYRICK CLINEAPPROVED

 04/26/2021COMPLETE PERMIT**RICK CLINEAPPROVED

BLDG FINAL CERT OF COMPRICK CLINE

FOOD AND LODGINGRONDA HARTAPPROVEDF&L FINAL INSPECT APPROVED BY AC 4/28/21