| LOCATION SETBACKS | | | | |
|
01/30/2020 | GRADING COM | RANDALL MOORE | APPROVED | | |
|
| LOW VOLTAGE ROUGH | | | | |
|
| LOW VOLTAGE FINAL | | | | |
|
02/10/2020 | FOOTING | RICK CLINE | PARTIAL | | 2/10/2020 9:19:05 AM
pier footings need engineers report
|
|
02/17/2020 | ELEC UNDERGROUND | GERALD JOHNSON | REJECTED | Request afternoon inspection | 2/14/2020 1:38:50 PM
2/14/2020 1:38 PM KELLER ELECTRIC COMPANY INC
Service Entrance conduits
See Dustin Caudill foreman for Keller Electric Co. on-site cell#336-452-7279.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
2/17/2020 11:47:17 AM
not ready
|
|
02/18/2020 | ELEC UNDERGROUND | GERALD JOHNSON | REJECTED | Request late afternoon inspection | 2/17/2020 11:47:21 AM
not ready
2/17/2020 11:47:21 AM
2/14/2020 1:38 PM KELLER ELECTRIC COMPANY INC
Service Entrance conduits
See Dustin Caudill foreman for Keller Electric Co. on-site cell#336-452-7279.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
2/17/2020 11:59:43 AM
2/17/2020 11:59 AM KELLER ELECTRIC COMPANY INC
Service Entrance underground & UFER. See Dustin Caudill 336-452-7279.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
2/18/2020 2:13:00 PM
not ready
|
|
02/20/2020 | ELEC UNDERGROUND | DARIN OXENTINE | PARTIAL | Service Entrance Underground | 2/18/2020 2:13:05 PM
not ready
2/18/2020 2:13:06 PM
2/14/2020 1:38 PM KELLER ELECTRIC COMPANY INC
Service Entrance conduits
See Dustin Caudill foreman for Keller Electric Co. on-site cell#336-452-7279.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
2/18/2020 2:13:06 PM
not ready
2/18/2020 2:13:06 PM
2/17/2020 11:59 AM KELLER ELECTRIC COMPANY INC
Service Entrance underground & UFER. See Dustin Caudill 336-452-7279.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
2/18/2020 3:02:22 PM
2/18/2020 3:02 PM KELLER ELECTRIC COMPANY INC
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
2/20/2020 10:04:25 AM
rebar bond and conduits for service
|
|
| WATER SUPPLY | | | | |
|
02/25/2020 | PLUMBING SLAB | RICK CLINE | PARTIAL | AM PLEASE | 2/21/2020 12:02:07 PM
partial underground
2/25/2020 1:30:16 PM
marked on plans
|
|
02/26/2020 | WATER SUPPLY | RICK CLINE | APPROVED | eTRAKiT Inspection Request | 2/25/2020 1:23:28 PM
2/25/2020 1:23 PM O.H. PLUMBING INC
Contact Name: O.H. PLUMBING INC
Site Address: 1243 TONEWOOD ST
Phone: 3362400338
e-Mail: OHPLUMBING@LEXCOMINC.NET
|
|
03/02/2020 | FOOTING | RICK CLINE | PARTIAL | | 3/2/2020 1:33:02 PM
3rd party
|
|
03/03/2020 | ELECTRICAL SLAB | DARIN OXENTINE | REJECTED | Site Contact Dustin Caudill 336-452-7279 | 2/28/2020 12:18:06 PM
2/28/2020 12:18 PM KELLER ELECTRIC COMPANY INC
Partial Electrical underground Slab Rough.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
3/3/2020 1:00:59 PM
canceled
|
|
03/05/2020 | FOOTING | RICK CLINE | PARTIAL | | 3/2/2020 1:33:07 PM
3rd party
3/5/2020 9:59:58 AM
need 3rd party report
|
|
| FOOTING | RICK CLINE | | | 3/5/2020 10:00:02 AM
3rd party
3/5/2020 10:00:02 AM
need 3rd party report
|
|
03/05/2020 | FOUNDATION | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 2/17/2020 3:13:47 PM
2/17/2020 3:13 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
3/5/2020 10:00:03 AM
need 3rd party report
|
|
03/05/2020 | ELECTRICAL SLAB | | PARTIAL | Request AM inspections-Elect. slab rough | 3/5/2020 2:01:31 PM
3/5/2020 2:01 PM KELLER ELECTRIC COMPANY INC
See foreman Dustin Caudill 336-452-7279.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
3/5/2020 2:16:31 PM
conduits to floor boxes
|
|
03/13/2020 | ELECTRICAL SLAB | DARIN OXENTINE | PARTIAL | Floor Boxes | 3/12/2020 11:34:55 AM
3/12/2020 11:34 AM KELLER ELECTRIC COMPANY INC
floor box installation
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
3/13/2020 12:12:27 PM
floor boxes in office area
|
|
| ELECTRICAL SLAB | | | Floor Boxes | |
|
03/13/2020 | FOUNDATION | DARIN OXENTINE | PARTIAL | eTRAKiT Inspection Request | 3/5/2020 10:00:08 AM
need 3rd party report
3/5/2020 10:00:08 AM
2/17/2020 3:13 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
3/12/2020 6:50:27 AM
3/12/2020 6:50 AM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
3/13/2020 12:14:09 PM
foundation wall for elevator. concrete is being 3rd party inspected. rebar ok ok per plan
|
|
03/17/2020 | PLUMBING SLAB | RICK CLINE | APPROVED | | |
|
03/17/2020 | SLAB | RICK CLINE | APPROVED | eTRAKiT Inspection Request | 3/16/2020 7:33:35 AM
3/16/2020 7:33 AM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
|
|
03/17/2020 | PLUMBING SLAB | RICK CLINE | APPROVED | | |
|
| FOUNDATION | | | masonry | |
|
04/17/2020 | SHEATHING AND FLASHING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 4/16/2020 3:44:52 PM
4/16/2020 3:44 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
4/17/2020 10:39:57 AM
consultation
|
|
04/22/2020 | FRAMING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 4/21/2020 10:20:45 AM
4/21/2020 10:20 AM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
4/22/2020 2:43:52 PM
consult
|
|
05/22/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | REJECTED | Requesting Consult by phone proposed box | 5/21/2020 11:33:05 AM
5/21/2020 11:33 AM KELLER ELECTRIC COMPANY INC
Sent D. Oxentine email requesting approval of outlet boxes. Please call Tom Keller @ 336-667-9479 asap.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
5/22/2020 2:01:23 PM
(canceled)
|
|
| SHEATHING AND FLASHING | GERALD JOHNSON | | eTRAKiT Inspection Request | 5/18/2020 9:11:50 AM
5/18/2020 9:11 AM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
|
|
07/01/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | INCOMPLETE | eTRAKiT Inspection Request | 5/22/2020 2:01:28 PM
(canceled)
5/22/2020 2:01:28 PM
5/21/2020 11:33 AM KELLER ELECTRIC COMPANY INC
Sent D. Oxentine email requesting approval of outlet boxes. Please call Tom Keller @ 336-667-9479 asap.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
6/30/2020 2:42:01 PM
6/30/2020 2:42 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
7/1/2020 9:20:26 AM
field consultation
|
|
07/15/2020 | FRAMING | DARIN OXENTINE | INCOMPLETE | eTRAKiT Inspection Request | 7/15/2020 10:27:17 AM
field consultation.
|
|
07/15/2020 | FRAMING | GERALD JOHNSON | APPROVED | eTRAKiT Inspection Request | |
|
07/24/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | INCOMPLETE | 4th Floor OH Electrical & Corridor Walls | 7/22/2020 10:46:21 AM
7/22/2020 10:46 AM KELLER ELECTRIC COMPANY INC
4th Floor OH Electrical & Corridor Walls See Dustin Caudill 336-452-7279.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
7/24/2020 11:51:15 AM
field consultation
|
|
07/29/2020 | MECHANICAL ROUGH | RICK CLINE | REJECTED | | 7/29/2020 3:01:45 PM
4th floor - installation is a deviation from the plan design. cannot tie the exhaust together.
|
|
07/29/2020 | FRAMING | RICK CLINE | PARTIAL | | 7/29/2020 3:04:25 PM
framing approved to allow the insulation installed in top trusses and corridor wall only
|
|
07/30/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | PARTIAL | 4th Floor OH Electrical & Corridor Walls | 7/30/2020 3:26:06 PM
above ceiling only on 4th floor
|
|
08/05/2020 | SEWER | DARIN OXENTINE | REJECTED | eTRAKiT Inspection Request | 8/4/2020 2:47:31 PM
8/4/2020 2:47 PM O.H. PLUMBING INC
sewer line and grease trap
Contact Name: O.H. PLUMBING INC
Site Address: 1243 TONEWOOD ST
Phone: 3362400338
e-Mail: OHPLUMBING@LEXCOMINC.NET
8/5/2020 3:58:07 PM
install 2 '' vent for grease trap per plan.
|
|
08/06/2020 | SEWER | RICK CLINE | REJECTED | eTRAKiT Inspection Request | 8/6/2020 11:24:51 AM
Vented lids are code compliant but must be approved and documented by the designer.
|
|
08/06/2020 | FRAMING | RICK CLINE | PARTIAL | | 8/6/2020 11:30:15 AM
1st floor ceiling for insultion
|
|
08/07/2020 | SEWER | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 8/6/2020 5:35:37 AM
8/6/2020 5:35 AM O.H. PLUMBING INC
Contact Name: O.H. PLUMBING INC
Site Address: 1243 TONEWOOD ST
Phone: 3362400338
e-Mail: OHPLUMBING@LEXCOMINC.NET
8/7/2020 2:11:01 PM
down to the road
|
|
08/07/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | REJECTED | 3th&4th Floor OH Electrical | 8/7/2020 2:12:23 PM
finish fire caulking on 3rd floor
|
|
08/13/2020 | MECHANICAL ROUGH | RICK CLINE | PARTIAL | 4th FLOOR. WALL | 8/13/2020 9:37:34 AM
4th floor only, fire caulk in chase walls for bath fan exhaust.
|
|
08/13/2020 | MECHANICAL ROUGH | RICK CLINE | PARTIAL | | 8/13/2020 2:53:03 PM
PE approval letter for the bath fan exhaust system is attached
|
|
08/13/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | REJECTED | 3rd Floor OH | 8/12/2020 12:45:12 PM
8/12/2020 12:45 PM KELLER ELECTRIC COMPANY INC
3rd Floor OH rough Electrical
See David Miller 336-957-0001
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
8/13/2020 3:48:38 PM
(finish fire caulking around conduits.)
|
|
08/14/2020 | FRAMING | RICK CLINE | INCOMPLETE | eTRAKiT Inspection Request | 8/13/2020 4:42:16 PM
8/13/2020 4:42 PM ben Taylor
OH for 3rd floor. Plumbing is supposed to be called in also. There isn''t any HVAC required for the 3rd floor.
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
|
|
08/17/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | REJECTED | | 8/13/2020 3:48:43 PM
(finish fire caulking around conduits.)
8/13/2020 3:48:43 PM
8/12/2020 12:45 PM KELLER ELECTRIC COMPANY INC
3rd Floor OH rough Electrical
See David Miller 336-957-0001
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
8/14/2020 2:50:28 PM
8/14/2020 2:50 PM KELLER ELECTRIC COMPANY INC
Please see David Miller 336-957-0001 prior to 3 PM
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
8/17/2020 3:27:09 PM
(4th floor wall rough) missing putty pads. can not use firestop box inserts when boxes are back to back per manufacture. missing knock out fillers. missing pads throughout the building and need to use putty pads for stud cavities with more than 16 square inches and where boxes are back to back. need engineer approval for plastic boxes in the bathrooms.
|
|
08/17/2020 | FRAMING | RICK CLINE | REJECTED | 3rd and 4th floors | 8/14/2020 3:40:37 PM
8/14/2020 3:40 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
8/17/2020 3:54:12 PM
3rd and 4th floors - electrical inspection is failed
|
|
08/06/2020 | INSULATION | RICK CLINE | PARTIAL | 4th floor - ceiling and corridor walls o | 8/5/2020 9:01:12 AM
8/5/2020 9:01 AM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
8/6/2020 11:27:21 AM
4th floor - ceiling and corridor walls only
|
|
07/06/2020 | FRAMING | RICK CLINE | PARTIAL | 4th OH | 6/29/2020 2:36:19 PM
6/29/2020 2:36 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
7/6/2020 10:55:10 AM
Roof trusses only. Batt insulation may be installed after roof is complete, all trades installations is under insulation.
|
|
09/03/2020 | FRAMING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 9/2/2020 6:48:33 AM
9/2/2020 6:48 AM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/3/2020 10:13:43 AM
2nd floor, all bathrooms and mech room excluded, overhead may be insulated. 3rd floor overhead except bathrooms and mech room may be sheet rocked.
|
|
09/14/2020 | FRAMING | RICK CLINE | REJECTED | eTRAKiT Inspection Request | 9/10/2020 3:32:47 PM
9/10/2020 3:32 PM ben Taylor
4th floor wall framing for insulation
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/14/2020 3:54:29 PM
the electrical inspection failed
|
|
09/15/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | REJECTED | 4th Floor Wall Rough Electrical | 8/20/2020 11:00:54 AM
8/20/2020 11:00 AM KELLER ELECTRIC COMPANY INC
See David Miller on-site prior to 3:00PM contact # 336-957-0001. Requesting 3rd Floor OH rough elect. inspection
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
9/10/2020 4:26:58 PM
9/10/2020 4:26 PM KELLER ELECTRIC COMPANY INC
See David Miller prior to 3:00 PM- 336-957-0001 for all 4th Floor wall electrical rough
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
9/15/2020 2:28:52 PM
(install putty pads where requirered see artical 714 of 2018 building code)
|
|
09/22/2020 | PLUMBING ROUGH | RICK CLINE | PARTIAL | 7046228389 | 9/21/2020 4:24:31 PM
9/21/2020 4:24 PM ben Taylor
Half of 4th floor. Only able to test half the floor at the time
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/22/2020 3:36:15 PM
DWV and Water distribution on 4th floor north end to the mech room, fire caulking and roof drains are incomplete.
|
|
09/22/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | PARTIAL | 4th Floor Electrical Wall Rough | 9/15/2020 2:29:00 PM
(install putty pads where requirered see artical 714 of 2018 building code)
9/15/2020 2:29:00 PM
8/20/2020 11:00 AM KELLER ELECTRIC COMPANY INC
See David Miller on-site prior to 3:00PM contact # 336-957-0001. Requesting 3rd Floor OH rough elect. inspection
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
9/15/2020 2:29:00 PM
9/10/2020 4:26 PM KELLER ELECTRIC COMPANY INC
See David Miller prior to 3:00 PM- 336-957-0001 for all 4th Floor wall electrical rough
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
9/17/2020 11:49:34 AM
9/17/2020 11:49 AM KELLER ELECTRIC COMPANY INC
4th Floor Electrical Wall Rough - AM inspection request min. prior to 3 PM.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
9/18/2020 1:21:28 PM
9/18/2020 1:21 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 4th Floor Rough Wall inspection - request AM or prior to 3PM latest.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
9/22/2020 4:46:21 PM
guest rooms 4th floor
|
|
09/22/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | PARTIAL | 3 rd floor am | 9/22/2020 4:47:03 PM
guest rooms 3th floor
|
|
09/23/2020 | FRAMING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 9/17/2020 7:49:53 AM
9/17/2020 7:49 AM ben Taylor
2 floor over head
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/17/2020 2:44:30 PM
9/17/2020 2:44 PM ben Taylor
2 floor over head
4 floor guess room walls
1 floor corridor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/18/2020 2:04:54 PM
NOT READY
9/23/2020 11:15:03 AM
3rd floor framing
|
|
09/23/2020 | FRAMING | RICK CLINE | APPROVED | eTRAKiT Inspection Request | 9/22/2020 4:30:06 PM
9/22/2020 4:30 PM ben Taylor
3rd floor framing except for RRs.
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/23/2020 7:33:23 PM
3rd floor framing except for RRs
|
|
09/24/2020 | PLUMBING ROUGH | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 9/15/2020 2:06:42 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/16/2020 3:24:25 PM
cancelled
9/24/2020 10:56:29 AM
remaining 4th floor DWV and water distribution (not insulated)
|
|
| PLUMBING ROUGH | RICK CLINE | | | 9/24/2020 10:56:39 AM
remaining 4th floor DWV and water distribution (not insulated)
9/24/2020 10:56:39 AM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/24/2020 10:56:39 AM
cancelled
10/6/2020 11:07:12 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:39 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:39 AM
3rd floor dwv, no insulation installed
1/22/2021 3:17:03 PM
remaining 4th floor DWV and water distribution (not insulated)
1/22/2021 3:17:08 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/22/2021 3:17:08 PM
cancelled
1/22/2021 3:17:11 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:14 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:14 PM
3rd floor dwv, no insulation installed
1/22/2021 3:17:17 PM
marked on plans - phase 3 rough
1/26/2021 3:15:30 PM
1st floor guest rooms and laundry
1/26/2021 3:15:31 PM
1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC
Site Contact: David Ryan 704-437-0357
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
1/26/2021 3:15:31 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:31 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:31 PM
cancelled
1/26/2021 3:15:31 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:32 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:32 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:32 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:32 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:32 PM
cancelled
1/26/2021 3:15:32 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:32 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:32 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:32 PM
marked on plans - phase 3 rough
|
|
09/24/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | REJECTED | 1st & 2nd FL GR Wall Rough | 9/23/2020 1:49:21 PM
9/23/2020 1:49 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 1st & 2nd Floor Guestroom Wall Rough. Prior to 3:00PM please.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
9/24/2020 12:48:56 PM
missing nail guards, plaster ring, ko filler and fire caulking.
|
|
09/29/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | PARTIAL | 2nd Floor Wall Rough | 9/24/2020 2:07:10 PM
9/24/2020 2:07 PM KELLER ELECTRIC COMPANY INC
Please see David Miller(Keller Elect.) foreman contact =336-957-0001. Reinspect 1st&2nd GR Walls. David is on site from 8AM to Noon and 1PM till 3PM - please call David at above number to coordinate and assist in inspections.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
|
|
09/30/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | REJECTED | 1st Floor Guest Rooms Wall Rough | 9/29/2020 3:18:20 PM
9/29/2020 3:18 PM KELLER ELECTRIC COMPANY INC
Request AM please see David Miller 336-957-0001 for 1st FL GR Wall Rough Elect. request prior to noon and 3:00PM
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
9/30/2020 1:46:15 PM
wire door bell in handicap rooms
|
|
09/30/2020 | INSULATION | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 9/23/2020 4:43:48 PM
9/23/2020 4:43 PM ben Taylor
4 floor insulation walls
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/24/2020 10:53:47 AM
4th floor rooms
9/30/2020 2:39:39 PM
3rd floor rooms
|
|
09/30/2020 | FRAMING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 9/23/2020 11:15:27 AM
3rd floor framing
9/23/2020 11:15:27 AM
9/17/2020 7:49 AM ben Taylor
2 floor over head
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/23/2020 11:15:27 AM
9/17/2020 2:44 PM ben Taylor
2 floor over head
4 floor guess room walls
1 floor corridor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/23/2020 11:15:27 AM
NOT READY
9/29/2020 12:21:08 PM
9/29/2020 12:21 PM ben Taylor
3 floor walls, AM would be great if we could?
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/30/2020 2:39:44 PM
(2nd floor rooms only)
|
|
10/05/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | PARTIAL | 2nd Floor Guestroom walls | 10/2/2020 2:29:51 PM
10/2/2020 2:29 PM KELLER ELECTRIC COMPANY INC
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
|
|
10/06/2020 | INSULATION | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 10/5/2020 9:05:33 AM
10/5/2020 9:05 AM ben Taylor
1 floor common area and hallway
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
10/6/2020 10:14:41 AM
1st floor common area and hallway overhead in TGI
|
|
10/06/2020 | GAS PIPING ROUGH | RICK CLINE | REJECTED | | 10/6/2020 11:06:55 AM
fire chauk the floor penetrations to the roof
|
|
| GAS PIPING ROUGH | RICK CLINE | | | 10/6/2020 11:07:02 AM
fire chauk the floor penetrations to the roof
|
|
10/06/2020 | PLUMBING ROUGH | RICK CLINE | PARTIAL | | 10/6/2020 11:07:04 AM
roof drains test, need insulation and mid story straps
|
|
| PLUMBING ROUGH | RICK CLINE | | | 10/6/2020 11:07:12 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:40 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:40 AM
3rd floor dwv, no insulation installed
1/22/2021 3:17:25 PM
remaining 4th floor DWV and water distribution (not insulated)
1/22/2021 3:17:25 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/22/2021 3:17:26 PM
cancelled
1/22/2021 3:17:26 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:26 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:26 PM
3rd floor dwv, no insulation installed
1/22/2021 3:17:26 PM
marked on plans - phase 3 rough
1/26/2021 3:15:33 PM
1st floor guest rooms and laundry
1/26/2021 3:15:33 PM
1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC
Site Contact: David Ryan 704-437-0357
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
1/26/2021 3:15:33 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:33 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:33 PM
cancelled
1/26/2021 3:15:33 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:33 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:34 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:34 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:34 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:34 PM
cancelled
1/26/2021 3:15:34 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:34 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:34 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:34 PM
marked on plans - phase 3 rough
|
|
10/07/2020 | INSULATION | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 9/30/2020 2:39:43 PM
3rd floor rooms
9/30/2020 2:39:43 PM
9/23/2020 4:43 PM ben Taylor
4 floor insulation walls
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/30/2020 2:39:43 PM
4th floor rooms
10/6/2020 1:47:18 PM
10/6/2020 1:47 PM ben Taylor
2 floor walls
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
10/7/2020 4:12:46 PM
2nd floor - rooms and corridor
|
|
10/08/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | PARTIAL | 1st FL Guestroom and GR Corridor walls | 10/7/2020 1:37:02 PM
10/7/2020 1:37 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for rough electrical 1st Floor Guestroom and GR Corridor 152 wall rough. request AM min. prior to 3:00PM -David at lunch noon.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
|
|
10/14/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | PARTIAL | 1ST Floor Common Area walls | 10/9/2020 2:57:08 PM
10/9/2020 2:57 PM KELLER ELECTRIC COMPANY INC
request AM inspection 1st Floor Common Areas Electrical Walls rough. See David Miller 336-957-0001 prior to 3 PM or at lunch at noon.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
10/14/2020 10:48:21 AM
partial 1st floor wall rough pending pool area.
|
|
10/15/2020 | FRAMING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 9/30/2020 2:39:48 PM
3rd floor framing
9/30/2020 2:39:48 PM
9/17/2020 7:49 AM ben Taylor
2 floor over head
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/30/2020 2:39:48 PM
9/17/2020 2:44 PM ben Taylor
2 floor over head
4 floor guess room walls
1 floor corridor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/30/2020 2:39:48 PM
NOT READY
9/30/2020 2:39:48 PM
(2nd floor rooms only)
9/30/2020 2:39:48 PM
9/29/2020 12:21 PM ben Taylor
3 floor walls, AM would be great if we could?
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
10/8/2020 4:17:48 PM
10/8/2020 4:17 PM ben Taylor
1 floor rooms
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
10/15/2020 10:20:21 AM
4th floor guest room chase floor fire proofing, and 1st floor framing per engineers approval.
|
|
10/16/2020 | FRAMING | RICK CLINE | PARTIAL | 3rd floor chase floor fire proofing | 10/16/2020 9:19:23 AM
3rd floor chase floor fire proofing
|
|
10/20/2020 | PLUMBING ROUGH | RICK CLINE | INCOMPLETE | eTRAKiT Inspection Request | 9/24/2020 10:56:40 AM
remaining 4th floor DWV and water distribution (not insulated)
9/24/2020 10:56:40 AM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/24/2020 10:56:41 AM
cancelled
10/6/2020 11:07:10 AM
roof drains test, need insulation and mid story straps
10/19/2020 4:49:24 PM
10/19/2020 4:49 PM ben Taylor
4th floor HW and roof drain insulation
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
10/20/2020 9:34:34 AM
cancelled
10/29/2020 10:36:37 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:37 AM
3rd floor dwv, no insulation installed
|
|
10/21/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | REJECTED | Temp/Perm Power MDP | 10/20/2020 2:09:39 PM
10/20/2020 2:09 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 Requesting Temp/Perm power to energize: MDP along with 1st FL Panels: DP1,IG & 4th FL Panel RM.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
10/21/2020 3:05:45 PM
need temp power permit.
|
|
10/22/2020 | INSULATION | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 10/7/2020 4:12:52 PM
3rd floor rooms
10/7/2020 4:12:52 PM
9/23/2020 4:43 PM ben Taylor
4 floor insulation walls
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
10/7/2020 4:12:52 PM
4th floor rooms
10/7/2020 4:12:52 PM
2nd floor - rooms and corridor
10/7/2020 4:12:52 PM
10/6/2020 1:47 PM ben Taylor
2 floor walls
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
10/21/2020 1:22:21 PM
10/21/2020 1:22 PM ben Taylor
rooms on 1 floor walls and overhead.
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
10/22/2020 2:59:05 PM
1st floor guest rooms
|
|
10/22/2020 | MECHANICAL ROUGH | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 10/20/2020 11:30:47 AM
10/20/2020 11:30 AM ben Taylor
chase wall duct seal
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
10/22/2020 3:00:16 PM
duct seal in chase and 3rd and 4th floor corridor
|
|
10/23/2020 | INSULATION | RICK CLINE | REJECTED | eTRAKiT Inspection Request | 10/7/2020 4:12:51 PM
3rd floor rooms
10/7/2020 4:12:51 PM
9/23/2020 4:43 PM ben Taylor
4 floor insulation walls
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
10/7/2020 4:12:51 PM
4th floor rooms
10/7/2020 4:12:52 PM
2nd floor - rooms and corridor
10/7/2020 4:12:52 PM
10/6/2020 1:47 PM ben Taylor
2 floor walls
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
10/22/2020 1:53:37 PM
10/22/2020 1:53 PM ben Taylor
chases walls gyp crete
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
|
|
10/26/2020 | TEMPORARY POWER | DARIN OXENTINE | APPROVED | | |
|
10/27/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | PARTIAL | Site Lighting Pole Bases | 10/26/2020 4:07:10 PM
10/26/2020 4:07 PM KELLER ELECTRIC COMPANY INC
Please see David Miller on-site contact cell# 336-957-0001 - request AM inspection of Site Lighting Pole Bases.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
10/27/2020 10:21:47 AM
pole bases ok.
|
|
10/27/2020 | PLUMBING ROUGH | RICK CLINE | PARTIAL | Partial wall rough | 9/23/2020 4:40:12 PM
9/23/2020 4:40 PM ben Taylor
2ed half of 4 floor pluming
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/24/2020 10:56:35 AM
remaining 4th floor DWV and water distribution (not insulated)
9/24/2020 10:56:35 AM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/24/2020 10:56:35 AM
cancelled
10/6/2020 11:07:10 AM
roof drains test, need insulation and mid story straps
10/26/2020 5:02:45 PM
10/26/2020 5:02 PM SERVICE PLUMBING OF CHARLOTTE INC
Please see Ron on site (704)799-5459
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
10/27/2020 2:49:49 PM
3rd floor DWV north end 15 rooms and water line tested on 2nd & 3rd floors
10/29/2020 10:36:38 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:38 AM
3rd floor dwv, no insulation installed
|
|
10/29/2020 | PLUMBING ROUGH | RICK CLINE | PARTIAL | 7046228389 | 10/6/2020 11:07:10 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:30 AM
3rd floor dwv, no insulation installed
|
|
| PLUMBING ROUGH | RICK CLINE | | 7046228389 | 10/29/2020 10:36:40 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:40 AM
3rd floor dwv, no insulation installed
1/22/2021 3:17:28 PM
remaining 4th floor DWV and water distribution (not insulated)
1/22/2021 3:17:28 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/22/2021 3:17:28 PM
cancelled
1/22/2021 3:17:29 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:29 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:29 PM
3rd floor dwv, no insulation installed
1/22/2021 3:17:29 PM
marked on plans - phase 3 rough
1/26/2021 3:15:35 PM
1st floor guest rooms and laundry
1/26/2021 3:15:35 PM
1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC
Site Contact: David Ryan 704-437-0357
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
1/26/2021 3:15:35 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:35 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:35 PM
cancelled
1/26/2021 3:15:35 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:35 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:35 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:35 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:36 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:36 PM
cancelled
1/26/2021 3:15:36 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:36 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:36 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:36 PM
marked on plans - phase 3 rough
|
|
10/29/2020 | PLUMBING ROUGH | RICK CLINE | APPROVED | Please see Ron on site - (704)799-5459 | 9/24/2020 10:56:37 AM
remaining 4th floor DWV and water distribution (not insulated)
9/24/2020 10:56:37 AM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/24/2020 10:56:37 AM
cancelled
10/6/2020 11:07:11 AM
roof drains test, need insulation and mid story straps
10/28/2020 3:49:20 PM
10/28/2020 3:49 PM SERVICE PLUMBING OF CHARLOTTE INC
Partial
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
10/29/2020 10:36:38 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:38 AM
3rd floor dwv, no insulation installed
10/29/2020 2:04:38 PM
3rd floor dwv and water not insulation
|
|
11/03/2020 | FRAMING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 10/29/2020 9:27:29 AM
10/29/2020 9:27 AM ben Taylor
Restroom walls
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
11/3/2020 10:02:29 AM
4th floor bath rooms rated wall seal, chase remains
|
|
11/03/2020 | INSULATION | RICK CLINE | INCOMPLETE | eTRAKiT Inspection Request | 10/29/2020 8:36:49 AM
10/29/2020 8:36 AM ben Taylor
furring channel
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
11/3/2020 10:03:31 AM
cancelled
|
|
11/04/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | PARTIAL | Partial Site Lighting Trench/Underground | 11/3/2020 4:01:21 PM
11/3/2020 4:01 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 Partial Site Lighting Underground/Trenching
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
11/4/2020 11:40:24 AM
pole lights
|
|
11/09/2020 | FRAMING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 11/6/2020 10:11:48 AM
11/6/2020 10:11 AM ben Taylor
chase wall detail inspection
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
11/9/2020 10:06:04 AM
4th floor bathroom chase walls and 3rd floor bathroom ceiling
|
|
11/09/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | REJECTED | eTRAKiT Inspection Request | 11/6/2020 10:10:59 AM
11/6/2020 10:10 AM ben Taylor
pool grounding on rebar
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
11/9/2020 2:57:25 PM
wrong inspection pool permit # is AP-310425
|
|
11/12/2020 | FRAMING | RICK CLINE | REJECTED | not ready | 11/10/2020 3:51:30 PM
11/10/2020 3:51 PM ben Taylor
chase walls on 3
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
11/12/2020 10:11:33 AM
not ready
|
|
11/17/2020 | FRAMING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 11/13/2020 2:06:31 PM
11/13/2020 2:06 PM ben Taylor
4 floor fire calking
3 rr ceiling
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
11/16/2020 2:22:41 PM
11/16/2020 2:22 PM ben Taylor
chase walls 3 floor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
|
|
11/19/2020 | ELEC UNDERGROUND | DARIN OXENTINE | PARTIAL | pm inspection please | 11/19/2020 9:00:26 AM
site lights
|
|
| ELEC UNDERGROUND | | | pm inspection please | |
|
11/19/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | PARTIAL | 4th Floor Guestroom OH Electrical | 11/13/2020 10:04:42 AM
11/13/2020 10:04 AM KELLER ELECTRIC COMPANY INC
Please coordinate with David Miller 336-957-0001 for 4th Guest room OH Electrical Inspections .
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
|
|
11/24/2020 | MECHANICAL ROUGH | RICK CLINE | PARTIAL | duct seal; marked on the plans | 11/23/2020 11:37:02 AM
11/23/2020 11:37 AM ben Taylor
duct seal for 1 and 2 floors
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
11/24/2020 2:45:33 PM
duct seal; marked on the plans
|
|
11/24/2020 | FRAMING | RICK CLINE | PARTIAL | 4th floor; marked on plans | 11/23/2020 11:32:17 AM
11/23/2020 11:32 AM ben Taylor
3,4, floor overhead restroom and foyer ceiling
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
11/24/2020 2:46:50 PM
4th floor; marked on plans
|
|
11/30/2020 | INSULATION | RICK CLINE | REJECTED | eTRAKiT Inspection Request | 11/24/2020 10:57:31 AM
11/24/2020 10:57 AM ben Taylor
Exterior wall on 1 floor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
11/30/2020 1:18:16 PM
not ready
|
|
| INSULATION | RICK CLINE | | eTRAKiT Inspection Request | 11/30/2020 1:18:31 PM
not ready
11/30/2020 1:18:31 PM
11/24/2020 10:57 AM ben Taylor
Exterior wall on 1 floor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
|
|
| INSULATION | RICK CLINE | | eTRAKiT Inspection Request | 11/30/2020 1:18:29 PM
not ready
11/30/2020 1:18:29 PM
11/24/2020 10:57 AM ben Taylor
Exterior wall on 1 floor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
|
|
12/01/2020 | FRAMING | RICK CLINE | PARTIAL | 4th floor; marked on plans | 11/30/2020 3:49:47 PM
11/30/2020 3:49 PM ben Taylor
3 floor overhead in restrooms
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
12/1/2020 2:55:08 PM
3rd floor above ceiling inspection in rooms and foyer only. 4 inch commode riser must have a collar and some rooms (marked on plans) are not ready for dry wall.
|
|
12/02/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | REJECTED | 4th Floor Guestroom OH Electrical | 12/1/2020 5:03:05 PM
12/1/2020 5:03 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 4th Floor Electrical Panels to energize for testing GR & operate PTACs
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
12/1/2020 5:14:19 PM
12/1/2020 5:14 PM KELLER ELECTRIC COMPANY INC
See David Miller=336-957-0001 for 4th Floor Electrical Panels Inspection (for testing and to energize PTACs on 4th) & 3rd floor guestroom OH Electrical.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
12/2/2020 2:33:20 PM
(finish door bells)
|
|
| MECHANICAL ABOVE CEILING | | | | |
|
12/04/2020 | FRAMING | RICK CLINE | APPROVED | 4th floor; marked on plans | 12/1/2020 2:55:14 PM
3rd floor above ceiling inspection in rooms and foyer only. 4 inch commode riser must have a collar and some rooms (marked on plans) are not ready for dry wall.
12/1/2020 2:55:14 PM
11/30/2020 3:49 PM ben Taylor
3 floor overhead in restrooms
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
12/3/2020 11:00:59 AM
12/3/2020 11:00 AM ben Taylor
3 floor overhead restrooms
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
12/4/2020 3:00:03 PM
all framing is complete, use above ceiling inspection request
|
|
12/11/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | REJECTED | 3rd FL Panels & 2nd G Rooms OH rough | 12/2/2020 2:33:23 PM
(finish door bells)
12/2/2020 2:33:23 PM
12/1/2020 5:03 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 4th Floor Electrical Panels to energize for testing GR & operate PTACs
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
12/2/2020 2:33:23 PM
12/1/2020 5:14 PM KELLER ELECTRIC COMPANY INC
See David Miller=336-957-0001 for 4th Floor Electrical Panels Inspection (for testing and to energize PTACs on 4th) & 3rd floor guestroom OH Electrical.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
12/10/2020 5:43:20 PM
12/10/2020 5:43 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 3rd Floor Panel inspection for the purpose of Operating PTACs and Testing along with 3rd Floor Guestroom OH Electrical Rough.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
12/10/2020 5:50:14 PM
12/10/2020 5:50 PM KELLER ELECTRIC COMPANY INC
3rd Floor panels to operate PTACs and testing & 2nd Floor Guestroom OH electrical Rough
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
12/11/2020 10:11:54 AM
canceled
|
|
12/16/2020 | BUILDING ABOVE CEILING | RICK CLINE | INCOMPLETE | eTRAKiT Inspection Request | 12/14/2020 1:10:58 PM
12/14/2020 1:10 PM ben Taylor
2 floor restroom furors
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
12/16/2020 7:13:38 AM
cancelled
|
|
12/16/2020 | ELECTRICAL ROUGH | DARIN OXENTINE | PARTIAL | 3rd Floor panels to operated PTACs /test | 12/14/2020 12:10:55 PM
12/14/2020 12:10 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 to inspect 3rd floor panels to operate PTAC''s & Testing
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
|
|
12/16/2020 | ELEC ABOVE CEILING | DARIN OXENTINE | PARTIAL | | |
|
12/16/2020 | ELEC ABOVE CEILING | DARIN OXENTINE | PARTIAL | 2nd FL GR OH Rough | 12/15/2020 11:45:25 AM
12/15/2020 11:45 AM KELLER ELECTRIC COMPANY INC
See David Miller for 2nd Floor Guest Rooms OH Electrical Rough inspection.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
|
|
12/18/2020 | PLUMBING ROUGH | RICK CLINE | REJECTED | Partial 1st floor rough | 9/24/2020 10:56:36 AM
remaining 4th floor DWV and water distribution (not insulated)
9/24/2020 10:56:36 AM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/24/2020 10:56:36 AM
cancelled
10/6/2020 11:07:11 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:38 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:38 AM
3rd floor dwv, no insulation installed
12/17/2020 5:19:43 PM
12/17/2020 5:19 PM SERVICE PLUMBING OF CHARLOTTE INC
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
12/18/2020 1:55:04 PM
north end of 1st- install mid story guides, support wtr lines and insulate, install fire stops (tests are good)
|
|
12/23/2020 | PLUMBING ROUGH | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 9/24/2020 10:56:38 AM
remaining 4th floor DWV and water distribution (not insulated)
9/24/2020 10:56:38 AM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/24/2020 10:56:38 AM
cancelled
10/6/2020 11:07:11 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:38 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:39 AM
3rd floor dwv, no insulation installed
12/22/2020 1:56:50 PM
12/22/2020 1:56 PM ben Taylor
phase 1 and 2 DWV and water
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
12/23/2020 4:04:58 PM
1st floor phase 1 walls only
12/28/2020 8:11:14 AM
1st floor phase 1 walls only
|
|
01/04/2021 | BUILDING ABOVE CEILING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 12/23/2020 5:16:12 PM
12/23/2020 5:16 PM ben Taylor
2 floor overhead ceiling guess rooms and restrooms
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/4/2021 1:39:41 PM
marked on the plans
|
|
01/05/2021 | ELECTRICAL ROUGH | DARIN OXENTINE | PARTIAL | see notes | 1/4/2021 2:57:40 PM
4th floor corridor and all stairwells, 2nd floor electric panels
|
|
01/06/2021 | BUILDING ABOVE CEILING | RICK CLINE | REJECTED | 4th corridor & public gang toilet chase | 1/6/2021 3:45:41 PM
rejection is marked on the plans
|
|
01/08/2021 | BUILDING ABOVE CEILING | RICK CLINE | REJECTED | 4th floor AC in corridor | 1/7/2021 5:24:39 PM
1/7/2021 5:24 PM ben Taylor
We submitted an RFI for damper at elevator and came back that no damper was needed. See Will to discuss.
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/8/2021 10:19:44 AM
marked on the plans
|
|
01/13/2021 | BUILDING ABOVE CEILING | RICK CLINE | PARTIAL | 4th floor AC in corridor | 1/8/2021 10:19:50 AM
marked on the plans
1/8/2021 10:19:50 AM
1/7/2021 5:24 PM ben Taylor
We submitted an RFI for damper at elevator and came back that no damper was needed. See Will to discuss.
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/12/2021 7:10:25 AM
1/12/2021 7:10 AM ben Taylor
Please notify once on site.
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/13/2021 11:01:10 AM
4th floor over head is approved
|
|
01/15/2021 | ELEC ABOVE CEILING | DARIN OXENTINE | PARTIAL | 3rd Floor Corridor Above Ceilings | 1/13/2021 4:23:32 PM
1/13/2021 4:23 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 requesting 3rd Floor corridor above ceiling inspection.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
1/15/2021 8:51:46 AM
3rd floor corridor above ceiling
|
|
01/20/2021 | BUILDING ABOVE CEILING | DARIN OXENTINE | PARTIAL | 4th floor AC in corridor | 1/13/2021 11:01:26 AM
marked on the plans
1/13/2021 11:01:26 AM
1/7/2021 5:24 PM ben Taylor
We submitted an RFI for damper at elevator and came back that no damper was needed. See Will to discuss.
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/13/2021 11:01:26 AM
4th floor over head is approved
1/13/2021 11:01:27 AM
1/12/2021 7:10 AM ben Taylor
Please notify once on site.
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/18/2021 3:12:59 PM
1/18/2021 3:13 PM ben Taylor
3rd floor above ceiling inspection
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/20/2021 3:13:28 PM
3rd floor corridor
|
|
01/22/2021 | ELECTRICAL ROUGH | DARIN OXENTINE | INCOMPLETE | Panel 1A | 1/20/2021 2:40:42 PM
1/20/2021 2:40 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001, request PM inspection Panel 1A
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
1/22/2021 2:42:18 PM
canceled
|
|
01/22/2021 | PLUMBING ROUGH | RICK CLINE | PARTIAL | | 9/24/2020 10:56:38 AM
remaining 4th floor DWV and water distribution (not insulated)
9/24/2020 10:56:38 AM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/24/2020 10:56:39 AM
cancelled
10/6/2020 11:07:12 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:39 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:39 AM
3rd floor dwv, no insulation installed
1/22/2021 3:16:51 PM
marked on plans - phase 3 rough
|
|
| PLUMBING ROUGH | RICK CLINE | | Partial 1st floor rough | 1/22/2021 3:17:29 PM
remaining 4th floor DWV and water distribution (not insulated)
1/22/2021 3:17:29 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/22/2021 3:17:29 PM
cancelled
1/22/2021 3:17:29 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:30 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:30 PM
3rd floor dwv, no insulation installed
1/22/2021 3:17:30 PM
marked on plans - phase 3 rough
1/26/2021 3:15:36 PM
1st floor guest rooms and laundry
1/26/2021 3:15:36 PM
1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC
Site Contact: David Ryan 704-437-0357
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
1/26/2021 3:15:37 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:37 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:37 PM
cancelled
1/26/2021 3:15:37 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:37 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:37 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:37 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:37 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:37 PM
cancelled
1/26/2021 3:15:38 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:38 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:38 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:38 PM
marked on plans - phase 3 rough
|
|
| PLUMBING ROUGH | RICK CLINE | | eTRAKiT Inspection Request | 1/22/2021 3:17:30 PM
remaining 4th floor DWV and water distribution (not insulated)
1/22/2021 3:17:30 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/22/2021 3:17:30 PM
cancelled
1/22/2021 3:17:30 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:30 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:30 PM
3rd floor dwv, no insulation installed
1/22/2021 3:17:31 PM
marked on plans - phase 3 rough
1/26/2021 3:15:38 PM
1st floor guest rooms and laundry
1/26/2021 3:15:38 PM
1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC
Site Contact: David Ryan 704-437-0357
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
1/26/2021 3:15:38 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:38 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:39 PM
cancelled
1/26/2021 3:15:39 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:39 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:39 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:39 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:39 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:39 PM
cancelled
1/26/2021 3:15:39 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:39 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:40 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:40 PM
marked on plans - phase 3 rough
|
|
| PLUMBING ROUGH | RICK CLINE | | | 1/22/2021 3:17:31 PM
remaining 4th floor DWV and water distribution (not insulated)
1/22/2021 3:17:31 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/22/2021 3:17:31 PM
cancelled
1/22/2021 3:17:31 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:31 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:31 PM
3rd floor dwv, no insulation installed
1/22/2021 3:17:31 PM
marked on plans - phase 3 rough
1/26/2021 3:15:40 PM
1st floor guest rooms and laundry
1/26/2021 3:15:40 PM
1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC
Site Contact: David Ryan 704-437-0357
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
1/26/2021 3:15:40 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:40 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:40 PM
cancelled
1/26/2021 3:15:40 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:41 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:41 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:41 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:41 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:41 PM
cancelled
1/26/2021 3:15:41 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:41 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:41 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:41 PM
marked on plans - phase 3 rough
|
|
| PLUMBING ROUGH | RICK CLINE | | eTRAKiT Inspection Request | 1/22/2021 3:17:26 PM
remaining 4th floor DWV and water distribution (not insulated)
1/22/2021 3:17:26 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/22/2021 3:17:27 PM
cancelled
1/22/2021 3:17:27 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:27 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:27 PM
3rd floor dwv, no insulation installed
1/22/2021 3:17:27 PM
marked on plans - phase 3 rough
1/26/2021 3:15:42 PM
1st floor guest rooms and laundry
1/26/2021 3:15:42 PM
1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC
Site Contact: David Ryan 704-437-0357
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
1/26/2021 3:15:42 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:42 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:42 PM
cancelled
1/26/2021 3:15:42 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:42 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:43 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:43 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:43 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:43 PM
cancelled
1/26/2021 3:15:43 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:43 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:43 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:43 PM
marked on plans - phase 3 rough
|
|
| PLUMBING ROUGH | RICK CLINE | | Partial wall rough | 1/19/2021 11:40:21 AM
1/19/2021 11:40 AM SERVICE PLUMBING OF CHARLOTTE INC
Site contact: Ron (704)799-5459
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
1/22/2021 3:17:27 PM
remaining 4th floor DWV and water distribution (not insulated)
1/22/2021 3:17:27 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/22/2021 3:17:27 PM
cancelled
1/22/2021 3:17:28 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:28 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:28 PM
3rd floor dwv, no insulation installed
1/22/2021 3:17:28 PM
marked on plans - phase 3 rough
1/26/2021 3:15:44 PM
1st floor guest rooms and laundry
1/26/2021 3:15:44 PM
1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC
Site Contact: David Ryan 704-437-0357
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
1/26/2021 3:15:44 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:44 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:44 PM
cancelled
1/26/2021 3:15:44 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:44 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:44 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:44 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:45 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:45 PM
cancelled
1/26/2021 3:15:45 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:45 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:45 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:45 PM
marked on plans - phase 3 rough
|
|
01/26/2021 | PLUMBING ROUGH | RICK CLINE | PARTIAL | 1st floor rough complete | 9/24/2020 10:56:40 AM
remaining 4th floor DWV and water distribution (not insulated)
9/24/2020 10:56:40 AM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
9/24/2020 10:56:40 AM
cancelled
10/6/2020 11:07:12 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:39 AM
roof drains test, need insulation and mid story straps
10/29/2020 10:36:40 AM
3rd floor dwv, no insulation installed
1/22/2021 3:17:20 PM
remaining 4th floor DWV and water distribution (not insulated)
1/22/2021 3:17:23 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/22/2021 3:17:25 PM
cancelled
1/22/2021 3:17:25 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:25 PM
roof drains test, need insulation and mid story straps
1/22/2021 3:17:25 PM
3rd floor dwv, no insulation installed
1/22/2021 3:17:25 PM
marked on plans - phase 3 rough
1/25/2021 10:27:12 AM
1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC
Site Contact: David Ryan 704-437-0357
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
1/26/2021 3:15:10 PM
1st floor guest rooms and laundry
|
|
| PLUMBING ROUGH | RICK CLINE | | 1st floor rough complete | 1/26/2021 3:15:47 PM
1st floor guest rooms and laundry
1/26/2021 3:15:47 PM
1/25/2021 10:27 AM SERVICE PLUMBING OF CHARLOTTE INC
Site Contact: David Ryan 704-437-0357
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
1/26/2021 3:15:47 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:47 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:47 PM
cancelled
1/26/2021 3:15:47 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:47 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:48 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:48 PM
remaining 4th floor DWV and water distribution (not insulated)
1/26/2021 3:15:48 PM
9/15/2020 2:06 PM ben Taylor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/26/2021 3:15:48 PM
cancelled
1/26/2021 3:15:48 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:48 PM
roof drains test, need insulation and mid story straps
1/26/2021 3:15:48 PM
3rd floor dwv, no insulation installed
1/26/2021 3:15:49 PM
marked on plans - phase 3 rough
|
|
01/28/2021 | ELEC ABOVE CEILING | DARIN OXENTINE | REJECTED | 2nd Floor Corridor OH | 1/25/2021 2:59:15 PM
1/25/2021 2:59 PM KELLER ELECTRIC COMPANY INC
See David Miller for 2nd Floor Corridor OH inspection.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
1/28/2021 6:34:43 AM
tie two lights on south end of corridor to structure
|
|
02/01/2021 | ELECTRICAL ROUGH | DARIN OXENTINE | REJECTED | eTRAKiT Inspection Request | 1/29/2021 1:24:45 PM
1/29/2021 1:24 PM ben Taylor
Bonding on the pool equ.
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
2/1/2021 3:43:37 PM
wrong permit. pool permit # is AP-310425
|
|
| ELECTRICAL ROUGH | | | eTRAKiT Inspection Request | |
|
02/02/2021 | GAS PIPING FINAL | RICK CLINE | APPROVED | | |
|
02/02/2021 | MECHANICAL ROUGH | RICK CLINE | INCOMPLETE | Air test | 2/1/2021 3:19:07 PM
2/1/2021 3:19 PM SERVICE PLUMBING OF CHARLOTTE INC
Site contact: Ron (704)799-5459
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
2/2/2021 3:25:21 PM
this is a gas inspection request
|
|
| MECHANICAL ROUGH | | | | |
|
02/02/2021 | GAS PIPING ROUGH | RICK CLINE | APPROVED | | 10/6/2020 11:07:03 AM
fire chauk the floor penetrations to the roof
|
|
02/04/2021 | BUILDING ABOVE CEILING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 1/20/2021 3:13:33 PM
marked on the plans
1/20/2021 3:13:33 PM
1/7/2021 5:24 PM ben Taylor
We submitted an RFI for damper at elevator and came back that no damper was needed. See Will to discuss.
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/20/2021 3:13:33 PM
4th floor over head is approved
1/20/2021 3:13:33 PM
1/12/2021 7:10 AM ben Taylor
Please notify once on site.
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
1/20/2021 3:13:33 PM
3rd floor corridor
1/20/2021 3:13:33 PM
1/18/2021 3:13 PM ben Taylor
3rd floor above ceiling inspection
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
2/2/2021 10:03:42 AM
2/2/2021 10:03 AM ben Taylor
Chase wall in guess rooms rr
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
2/4/2021 2:24:07 PM
marked on plans
|
|
02/08/2021 | ELEC ABOVE CEILING | DARIN OXENTINE | REJECTED | 1st Floor partial OH hard ceilings right | 2/5/2021 11:09:54 AM
2/5/2021 11:09 AM KELLER ELECTRIC COMPANY INC
See David Miller: 336-957-0001, 1st Floor Partial OH -Right side of building - to cover hard ceiling areas only.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
2/8/2021 1:22:32 PM
missing covers, need access to all switches above hard ceiling, finish low volt, and mc cable can not be on the grid.
|
|
02/09/2021 | BUILDING ABOVE CEILING | RICK CLINE | INCOMPLETE | eTRAKiT Inspection Request | 2/8/2021 1:09:17 PM
2/8/2021 1:09 PM ben Taylor
Overhead phases 1 and 2.
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
2/9/2021 9:08:18 AM
cancelled
|
|
02/11/2021 | ELEC ABOVE CEILING | DARIN OXENTINE | PARTIAL | 1st Floor Partial OH Elect. Hard Ceiling | 2/9/2021 2:37:54 PM
2/9/2021 2:37 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 1st Floor Right Side-Partial OH Elect. Hard ceiling areas reinspection.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
|
|
02/15/2021 | BUILDING ABOVE CEILING | RICK CLINE | INCOMPLETE | eTRAKiT Inspection Request | 2/13/2021 9:36:10 AM
2/13/2021 9:36 AM ben Taylor
All sheetrock ceilings right side of lobby including corridor
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
|
|
02/16/2021 | ELEC ABOVE CEILING | DARIN OXENTINE | PARTIAL | OH Electrical Center Sect. hard ceilings | 2/15/2021 4:27:07 PM
2/15/2021 4:27 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 requesting OH Electrical for Center section Hard Ceilings = Lobby/Buffett drywall & wood ceilings of center section common areas.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
2/16/2021 12:19:33 PM
lobby area
|
|
02/16/2021 | BUILDING ABOVE CEILING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 2/15/2021 5:36:22 PM
2/15/2021 5:36 PM ben Taylor
phases 1 and 2
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
2/16/2021 2:35:16 PM
north end of 1st floor hard ceiling space only
|
|
02/17/2021 | BUILDING ABOVE CEILING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 2/16/2021 4:01:06 PM
2/16/2021 4:01 PM ben Taylor
lobby
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
2/17/2021 2:47:54 PM
hard ceiling only in lobby and vestibule
|
|
02/18/2021 | BUILDING ABOVE CEILING | RICK CLINE | REJECTED | eTRAKiT Inspection Request | 2/17/2021 4:46:46 PM
2/17/2021 4:46 PM ben Taylor
ceiling in the lobby
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
2/18/2021 11:20:45 AM
beams across lobby ceiling requires two layers of sheetrock
|
|
02/23/2021 | BUILDING ABOVE CEILING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 2/18/2021 11:20:56 AM
beams across lobby ceiling requires two layers of sheetrock
2/18/2021 11:20:56 AM
2/17/2021 4:46 PM ben Taylor
ceiling in the lobby
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
2/21/2021 10:43:52 AM
2/21/2021 10:43 AM ben Taylor
above ceiling on all still beams
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
2/23/2021 9:42:56 AM
beams wrapped
|
|
02/24/2021 | ELEC ABOVE CEILING | DARIN OXENTINE | PARTIAL | 1st Floor GR Baths OH rough & Vestibule | 2/23/2021 11:32:02 AM
2/23/2021 11:32 AM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 1st Floor GR Bathrooms OH rough
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
2/23/2021 12:14:41 PM
2/23/2021 12:14 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 1st Floor guestroom bathroom OH rough & front Vestibule OH rough.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
2/24/2021 11:27:48 AM
bathrooms 1st floor only
|
|
| ELEC ABOVE CEILING | DARIN OXENTINE | | 1st Floor above ceiling GR Entry & Room | 2/24/2021 11:28:00 AM
bathrooms 1st floor only
2/24/2021 11:28:00 AM
2/23/2021 11:32 AM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 1st Floor GR Bathrooms OH rough
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
2/24/2021 11:28:00 AM
2/23/2021 12:14 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 1st Floor guestroom bathroom OH rough & front Vestibule OH rough.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
2/25/2021 1:28:23 PM
2/25/2021 1:28 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 1st Floor Above Ceiling Guestroom Entry & Maintenance/Storage 143.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
3/2/2021 11:14:35 AM
10 guest rooms 1st floor ok to hang. Missing covers on 6x6 boxes, need to leave access doors open.
|
|
03/02/2021 | PLUMBING FINAL CERT OF COMP | RICK CLINE | PARTIAL | 2nd, 3rd & 4th Floors | 3/1/2021 10:19:22 AM
3/1/2021 10:19 AM SERVICE PLUMBING OF CHARLOTTE INC
Site contact: Ron (704)799-5459
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
3/2/2021 10:51:28 AM
2nd, 3rd, & 4th, all good except the tank flush handle must be on open side of room
|
|
| PLUMBING FINAL CERT OF COMP | | | 2nd, 3rd & 4th Floors | |
|
03/02/2021 | MECHANICAL FINAL CERT OF COMP | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 2/25/2021 3:33:49 PM
2/25/2021 3:33 PM ben Taylor
Mechanical final on 3 and 4 floors
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
3/2/2021 10:57:24 AM
2nd, 3rd, & 4th floors
|
|
03/02/2021 | BUILDING ABOVE CEILING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 3/2/2021 10:59:51 AM
guest room foyers on 1st floor ok to hang
|
|
03/02/2021 | ELEC ABOVE CEILING | DARIN OXENTINE | PARTIAL | GUEST ROOMS AND LAUNDRY ROOM | 3/3/2021 8:23:16 AM
10 guest rooms 1st floor ok to hang. Missing covers on 6x6 boxes, need to leave access doors open
|
|
03/02/2021 | ELECTRICAL FINAL CERT OF COMP | DARIN OXENTINE | REJECTED | 3rd and 4th floor | 3/3/2021 8:26:38 AM
Bath fans not working properly. GFI's and receptacles not tightened too tight. Missing covers on boxes. Need to cap wiring to mechanical blinds or install blinds. Occupancy sensors don't work properly in guest rooms. Switches recessed too far in boxes in bathrooms
|
|
03/02/2021 | TEMPORARY POWER | DARIN OXENTINE | APPROVED | renew 2/26-4/26/2021 | |
|
03/05/2021 | BUILDING ABOVE CEILING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 3/3/2021 3:47:02 PM
3/3/2021 3:47 PM ben Taylor
Landry and back of house
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
|
|
03/05/2021 | ELECTRICAL FINAL CERT OF COMP | DARIN OXENTINE | PARTIAL | 4th Floor Final Elect. | 3/4/2021 4:27:58 PM
3/4/2021 4:27 PM KELLER ELECTRIC COMPANY INC
See Josh Absher 336-426-4314 to reinspect 4th & 3rd Floor Final Electrical.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
3/5/2021 4:21:36 PM
4th floor only
|
|
03/05/2021 | ELEC ABOVE CEILING | DARIN OXENTINE | REJECTED | 1st Floor multi room OH Electrical | 3/4/2021 4:30:36 PM
3/4/2021 4:30 PM KELLER ELECTRIC COMPANY INC
See Josh Absher 336-426-4314 for 1st Floor: Guest Laundry, Guestroom Corridor, Food Prep, Board Room OH Electrical.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
3/5/2021 4:23:04 PM
lower or install box extensions in quest rooms.
|
|
03/09/2021 | ELEC ABOVE CEILING | DARIN OXENTINE | APPROVED | 1st Floor OH Electrical multi room | 3/8/2021 2:28:51 PM
3/8/2021 2:28 PM KELLER ELECTRIC COMPANY INC
See Josh Absher 336-426-4314 for 1st Floor: Guest Laundry, Guestroom Corridor, Food Prep, Board Room OH Electrical.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
|
|
03/11/2021 | BUILDING ABOVE CEILING | RICK CLINE | PARTIAL | eTRAKiT Inspection Request | 3/10/2021 3:32:57 PM
3/10/2021 3:32 PM ben Taylor
lobby, board room,
Contact Name: ben Taylor
Site Address: 1243 TONEWOOD ST
Phone: 7049600842
e-Mail: btaylor@myers-chapman.com
3/11/2021 10:18:10 AM
marked on the plans
|
|
| BUILDING ABOVE CEILING | | | eTRAKiT Inspection Request | |
|
03/12/2021 | ELECTRICAL FINAL CERT OF COMP | DARIN OXENTINE | PARTIAL | 3rd Floor Final Electrical | 3/11/2021 1:34:34 PM
3/11/2021 1:34 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 3rd Floor Final Electrical inspection.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
|
|
03/17/2021 | ELECTRICAL FINAL CERT OF COMP | DARIN OXENTINE | PARTIAL | 2nd Floor Final Electrical | 2/25/2021 1:24:56 PM
2/25/2021 1:24 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 4th Floor Final Electrical Inspection.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
3/2/2021 11:14:36 AM
Bath fans not working properly. GFI's and receptacles not tightened/too tight. Missing covers on boxes. Need to cap wiring to mechanical blinds or install blinds. Occupancy sensors don't work properly in guest rooms. Switches recessed too far in boxes in bathrooms.
3/15/2021 10:02:19 AM
3/15/2021 10:02 AM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 2nd Floor Final Electrical
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
3/17/2021 8:46:48 AM
2nd floor
|
|
03/29/2021 | ELECTRICAL FINAL CERT OF COMP | DARIN OXENTINE | PARTIAL | 1st floor guest rooms | 3/26/2021 11:01:37 AM
3/26/2021 11:01 AM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for final electrical inspection of 1st Floor Guestrooms, GR Corridor 152 & Guest Laundry 151.
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
3/29/2021 12:08:43 PM
1st floor guest rooms
|
|
| ELECTRICAL FINAL CERT OF COMP | | | 1st floor guest rooms | |
|
03/31/2021 | ELECTRICAL FINAL CERT OF COMP | DARIN OXENTINE | PARTIAL | roof ok | 3/30/2021 1:44:19 PM
3/30/2021 1:44 PM KELLER ELECTRIC COMPANY INC
See David Miller 336-957-0001 for 1st Floor Final Electrical
Contact Name: KELLER ELECTRIC COMPANY INC
Site Address: 1243 TONEWOOD ST
Phone: 3366679479
e-Mail: tom@kellernc.com
|
|
04/01/2021 | FIRE FINAL CERT OF COMP | C MAURY JENKINS | APPROVED | | |
|
04/07/2021 | BACKFLOW | Regina A Hoke | APPROVED | | |
|
04/12/2021 | ELECTRICAL FINAL CERT OF COMP | DARIN OXENTINE | APPROVED | roof ok | |
|
04/19/2021 | ZONING FINAL | ELAINE ANTHONY | APPROVED | | |
|
04/23/2021 | BLDG FINAL CERT OF COMP | RICK CLINE | REJECTED | | 4/23/2021 4:10:13 PM
sewer not approved, hole in corridor wall over laundry room, paint the gas pipe on roof, break room toilet grab bar not secure, remove locks from gang bath doors, install clean out cover in front yard, multible holes remain un caulked (Tim was with me). screens are prohibited on dryer duct terminations.
|
|
04/23/2021 | MECHANICAL FINAL CERT OF COMP | RICK CLINE | APPROVED | eTRAKiT Inspection Request | |
|
04/23/2021 | SEWER | RICK CLINE | REJECTED | eTRAKiT Inspection Request | 4/23/2021 11:10:48 AM
tracer wire is not in place
|
|
| SEWER | RICK CLINE | | eTRAKiT Inspection Request | 4/23/2021 11:10:56 AM
tracer wire is not in place
|
|
04/23/2021 | PLUMBING FINAL CERT OF COMP | RICK CLINE | APPROVED | Ron (704)799-5459 (Site Contact) | 2/25/2021 12:55:08 PM
2/25/2021 12:55 PM SERVICE PLUMBING OF CHARLOTTE INC
2nd, 3rd & 4th Floors
Contact Name: SERVICE PLUMBING OF CHARLOTTE INC
Site Address: 1243 TONEWOOD ST
Phone: 7048958998
e-Mail: jjones@serviceplumbing.net
|
|
04/26/2021 | BLDG FINAL CERT OF COMP | RICK CLINE | APPROVED | | 4/23/2021 4:13:37 PM
sewer not approved, hole in corridor wall over laundry room, paint the gas pipe on roof, break room toilet grab bar not secure, remove locks from gang bath doors, install clean out cover in front yard, multible holes remain un caulked (Tim was with me) screens on dryer vents are prohibited
|
|
04/26/2021 | SEWER | RICK CLINE | APPROVED | eTRAKiT Inspection Request | 4/23/2021 11:10:59 AM
tracer wire is not in place
|
|
04/26/2021 | CERT OF OCCUPANCY | RICK CLINE | APPROVED | | |
|
04/26/2021 | COMPLETE PERMIT** | RICK CLINE | APPROVED | | |
|
| BLDG FINAL CERT OF COMP | RICK CLINE | | | |
|
| FOOD AND LODGING | RONDA HART | APPROVED | F&L FINAL INSPECT APPROVED BY AC 4/28/21 | |
|